41
8.4.2 Cooling Mode
8.4.2.1 Compressor running rules:
The operation frequency of compressor after starting submits to following rule.
45
43
40
38
30
28
22
20
Fmax=F4
Fmax=F7
Fmax=F8
Fmax=F6
Fmax=F3
If users switch on AC by remote controller, the compressor will run at the Fmax frequency for 7
minutes according to the outdoor ambient temp. During the 7 minutes, the frequency limitation is active.
7 minutes later, the compressor running frequency will be controlled as below:
3.5
3.0
2.5
2.0
1.5
1.0
0.5
-0.5
-1.0
A
B
C
D
E
F
G
H
While the zones of A,B,C... are corresponding to different compressor running frequency.
Note:
When T1-Ts keeps in the same temp. zone for 3 minutes, the compressor will run as the below rules:
A~E: Increase the frequency to the higher level until to F8.
F: Keep the current frequency.
Содержание MOC-09CFN1-BS0W
Страница 1: ...9ASUL A1 1211 SERVICE MANUAL MIDEA AIRCONDITIONER DC INVERTER SPLIT WALL MOUNTED TYPE...
Страница 17: ...15 MS9A 18HRDN1 MP0W MS9A 18CRDN1 MS0W MS9A 18HRDN1 MS0W MS9A 24HRDN1 MP0W...
Страница 18: ...16 MS9A 09HRDN1 BQ0W MS9A 12HRDN1 BS0W B...
Страница 19: ...17 MS9A 24CRDN1 MP0W...
Страница 20: ...18 MS9A 24HRDN1 MS0W...
Страница 22: ...20 MOC 12CRDN1 MS0W MOC 12HRFN1 MS0W...
Страница 23: ...21 MOF 18HDN1 MP0W MOF 18CRFN1 MS0W...
Страница 24: ...22 MOF 18HRFN1 MS0W MOG 24HDN1 MP0W...
Страница 25: ...23 MOC 09HFN1 BQ0W MOC 12HFN1 BS0W MOF 24HDN1 MP0W...
Страница 26: ...24 MOG 24HDN1 MS0W MOF 24CDN1 MP0W...
Страница 38: ...36 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage...
Страница 58: ...56 E4 Reserved function...
Страница 72: ...70...