MCAC-ATSM-2014-09 R410A tropical air-cooled scroll chiller unit 60Hz
99
12.3.4 Wiring steps
Step
Content
1
Check the unit and ensure that it is connected with grounding wires correctly, to avoid leakage, and the
grounding devices should be mounted in strict accordance with the requirements of electrical engineering rules.
The grounding wires can prevent electric shock.
2
The control box of the main power switch must be mounted in a proper position.
3
Wiring connection holes of the main power should be provided with glue cushion.
4
The main power and neutral wires and grounding wires of power supply are led into the electric box of the unit.
5
The wires of the main power must pass the bonding clamp.
6
Wires should be connected firmly to the connection terminals A, B, C, and N.
7
Phase sequences must be consistent when the wires of the main power.
8
The main power should be located out of easy reach of non-professional maintenance personnel, to avoid
mal-operation and improve safety.
9
Connection of control wires of water flow switches: the wire leads (prepared by the user) of water flow switches
are connected to the connection terminals W1 and W2 of the main unit.
10
Connection of control wires of auxiliary electric heaters: the control wires of AC contactor of the auxiliary electric
heater must pass the connection terminals H1 and H2 of the main unit, as shown..
11
Connection of control wires of pump: the control wires of AC contactor of the pump must pass the connection
terminals P1 and P2 of the main unit, as shown.
12
The connection way of the wired controller connects with every signal wires from package units: signal wires P,
Q, E are connected in the same way of main wires connection method and accordingly connect to the terminals
P, Q, E in the wired controller.
H1
H2
P
o
w
e
r
s
u
p
p
ly
(2
2
0
-2
4
0
V
~
6
0
H
z
)
Overcurrent relay
Control coil of AC contactor
P1
P2
P
o
w
e
r
s
u
p
p
ly
(2
2
0
-2
4
0
V
~
6
0
H
z
)
Overcurrent relay
Control coil of AC contactor
Switch (For trial run of pump)
Содержание MGBT-F120W/PN1
Страница 28: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 29 60kW module ...
Страница 29: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 30 120kW module ...
Страница 30: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 31 180kW module ...
Страница 32: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 33 60kW module ...
Страница 33: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 34 120kW module ...
Страница 34: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 35 180kW module ...
Страница 36: ......
Страница 45: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 46 10 Exploded view 10 1 MGCT F30W PN1 ...
Страница 46: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 47 ...
Страница 48: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 49 MGCT D30W PN1 ...
Страница 49: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 50 ...
Страница 51: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 52 10 2 MGBT F60W PN1 ...
Страница 54: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 55 ...
Страница 55: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 56 ...
Страница 57: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 58 10 4 MGBT F180W PN1 ...
Страница 82: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 83 ...