R410A tropical air-cooled scroll chiller unit 60Hz MCAC-ATSM-2014-09
86
Performance tables are based at sea level. Elevations other than sea level affect the performance of the unit.
The decreased air density will reduce condenser capacity and reduce the unit
’s performance. For
performance at elevations other than sea level refer to Table 3. Maximum allowable altitude is 1800meters.
Evaporator temperature drop factors
Performance tables are based on a 5
o
C temperature drop through the evaporator. Adjustment factors for
applications with temperature ranges from 3
o
C to 6
o
C in follow table. Temperature drops outside this range
can affect the control system
’s capability to maintain acceptable control and are not recommended.
Fouling factor
Fouling refers to the accumulation of unwanted material on solid surfaces, most often in an aquatic
environment. The fouling material can consist of either living organisms (biofouling) or a non-living
substance (inorganic or organic). Fouling is usually distinguished from other surface-growth phenomena in
that it occurs on a surface of a component, system or plant performing a defined and useful function, and
that the fouling process impedes or interferes with this function.
Other terms used in the literature to describe fouling include: deposit formation, encrustation, crudding,
deposition, scaling, scale formation, slagging, and sludge formation. The last six terms have a more narrow
meaning than fouling within the scope of the fouling science and technology, and they also have meanings
outside of this scope; therefore, they should be used with caution.
Fouling phenomena are common and diverse, ranging from fouling of ship hulls, natural surfaces in the
marine environment (marine fouling), fouling of heat-transfer components through ingredients contained in
the cooling water or gases, and even the development of plaque or calculus on teeth, or deposits on solar
panels on Mars, among other examples.
Foreign matter in the chilled water system will adversely affect the heat transfer capability of the evaporator,
and could increase the pressure drop and reduce the water flow. To provide optimum unit operation, proper
water treatment must be maintained. Refer to the able as following.
Fouling Factor
ALTITUDE
(m)
Difference of water
inlet and outlet temp.
(
℃
)
Fouling Factor
0.018
℃
/kW
0.044m 2
℃
/kW
0.086m 2
℃
/kW
0.172m 2
℃
/kW
C
P
C
P
C
P
C
P
Sea level
3
1.036
1.077
1.019
1.076
0.991
0.975
0.963
0.983
4
1.039
1.101
1.022
1.080
0.994
0.996
0.971
0.984
5
1.045
1.105
1.028
1.086
1.000
1.000
0.977
0.989
6
1.051
1.109
1.034
1.093
1.006
1.004
0.983
0.994
600
3
1.024
1.087
1.008
1.064
0.980
0.984
0.951
0.991
4
1.027
1.111
1.011
1.068
0.983
1.005
0.959
0.992
5
1.034
1.115
1.017
1.074
0.989
1.009
0.965
0.997
6
1.043
1.115
1.026
1.084
0.998
1.009
0.973
0.999
1200
3
1.013
1.117
0.996
1.052
0.969
1.011
0.942
1.002
4
1.015
1.118
0.998
1.055
0.971
1.012
0.948
1.003
5
1.023
1.122
1.006
1.063
0.979
1.015
0.955
1.005
6
1.031
1.125
1.015
1.072
0.987
1.018
0.962
1.007
1800
3
1.002
1.128
0.986
1.042
0.959
1.021
0.935
1.007
4
1.005
1.129
0.989
1.045
0.962
1.022
0.941
1.010
5
1.012
1.132
0.995
1.051
0.968
1.024
0.945
1.012
6
1.018
1.134
1.001
1.058
0.974
1.026
0.949
1.014
C--Cooling capacity
P--Power
Содержание MGBT-F120W/PN1
Страница 28: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 29 60kW module ...
Страница 29: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 30 120kW module ...
Страница 30: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 31 180kW module ...
Страница 32: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 33 60kW module ...
Страница 33: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 34 120kW module ...
Страница 34: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 35 180kW module ...
Страница 36: ......
Страница 45: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 46 10 Exploded view 10 1 MGCT F30W PN1 ...
Страница 46: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 47 ...
Страница 48: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 49 MGCT D30W PN1 ...
Страница 49: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 50 ...
Страница 51: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 52 10 2 MGBT F60W PN1 ...
Страница 54: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 55 ...
Страница 55: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 56 ...
Страница 57: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 58 10 4 MGBT F180W PN1 ...
Страница 82: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 83 ...