MCAC-ATSM-2014-09 R410A tropical air-cooled scroll chiller unit 60Hz
97
resistance, flexible pipe resistance, pipe elbow and three-way resistance, two-way resistance or three-way
resistance, as well as filter resistance.
H4: the longest terminal resistance.
(2) Installation the pump
a. The pump should be installed at the water inlet pipe, both of which sides must mount the soft connectors
for vibration-proof.
b. The backup pump for the system (recommended).
c. Units must with a main unit controls (Please see
“4.5 fielding wiring” for the controls diagram).
12.3 Wiring Installation
All wiring installation should be done by qualified person.
12.3.1 Precautions:
1. The air-conditioner should apply special power supply, whose voltage should conform to rated voltage.
2. Wiring construction must be conducted by the professional technicians according to the labeling on the
circuit diagram.
3. Only use the electric components specified by our company, and require installation and technical
services from the manufacturer or authorized dealer. If wiring connection fails to conform to electric
installation norm, failure of the controller, electronic shock, and so on may be caused.
4. The connected fixed wires must be equipped with full switching-off devices with at least 3mm contact
separation.
5. Set leakage protective devices according to the requirements of national technical standard about electric
equipment.
6. After completing all wiring construction, conduct careful check before connecting the power supply.
7. Please carefully read the labels on the electric cabinet.
8. The user’s attempt to repair the controller is prohibited, since improper repair may cause electric shock,
damages to the controller, and so on. If the user has any requirement of repair, please contact the
maintenance center.
12.3.2 Power supply specification
Items
Model
Outdoor power supply
Wiring
Power supply
Manual switch
Fuse
MGCT-F30W/PN1
380V
~
3Ph
~
60Hz
50A
36A
10mm2
(<30m)
MGCT-D30W/PN1
380V
~
3Ph
~
60Hz
50A
36A
10mm2
(<30m)
MGBT-F60W/PN1
380V
~
3Ph
~
60Hz
125A
100A
16mm
2
(<20m)
MGBT-F120W/PN1
380V
~
3Ph
~
60Hz
200A
150A
Base on the actual distance of the
wire, more than 35 mm
2
for each
module
MGBT-F180W/PN1
380V
~
3Ph
~
60Hz
350A
300A
According to the actual distance of
wiring,70mm2 or lager for each unit.
12.3.3 Requirements of wiring connection
● No additional control components are required in the electric cabinet (such as relay, and so on), and the
power supply and control wires not connected with the electric cabinet are not allowed to go through the
electric box. Otherwise, electromagnetic interference may cause failure of the unit and control components
and even damages to them, which thus lead to protective failure.
● All cables led to the electrical box should be supported independently by the electric box.
Содержание MGBT-F120W/PN1
Страница 28: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 29 60kW module ...
Страница 29: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 30 120kW module ...
Страница 30: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 31 180kW module ...
Страница 32: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 33 60kW module ...
Страница 33: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 34 120kW module ...
Страница 34: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 35 180kW module ...
Страница 36: ......
Страница 45: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 46 10 Exploded view 10 1 MGCT F30W PN1 ...
Страница 46: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 47 ...
Страница 48: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 49 MGCT D30W PN1 ...
Страница 49: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 50 ...
Страница 51: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 52 10 2 MGBT F60W PN1 ...
Страница 54: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 55 ...
Страница 55: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 56 ...
Страница 57: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 58 10 4 MGBT F180W PN1 ...
Страница 82: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 83 ...