R410A tropical air-cooled scroll chiller unit 60Hz MCAC-ATSM-2014-09
132
Press this button at Check mode, when select the next modular, the operation status of the next modular will
display; if the current modular is 15#, and the next one is 0#.
Press this button for add address at wire address setting mode. If the wired controller address is 15, press
this key will display the next address is 0.
Press this button for add temperature at wire temperature setting mode.
Press this button for add clock or time at wire clock or time setting mode.
○
11 ADDRESS/- button
Press this button at query mode, when select the previous modular, the operation status of the previous
modular will display; if the current modular is 0#, and the previous one is 15#.
Press this button for minus address at wire address setting mode. If the wired controller address is 0, press
this key will display the next address is 15.
Press this button for minus temperature at wire temperature setting mode.
Press this button for minus clock or time at wire clock or time setting mode.
○
12
○
13 PAGEUP/DOWN button to spot check the operation parameters of unit in the main menu.
○
14 HYSTERESIS button (Hidden)
Use a small round bar with 1mm diameter to press this button, then can adjust the return parameter
δ=
(2,3,4,5
℃
). The numerical valve of hysteresis can be adjusted by
“
A
”
and
“
ADDRESS/-
”
, after
the adjustment then press the OK button for the setting confirmation.
The factory defaults
δ=
2
℃
.
○
15 LOCK button (Hidden)
Use a 1mm-diameter round bar to lock the current setting. Press this button again to unlock.
○
16 ADDRESS SET button (Hidden)
The address of wired controller can be set by pressing this button. The address range 0~15, therefore, 16
wired controller could be parallel at most.
When there is only one wired controller, it is necessary to execute this setting, the address of wired controller
should be set to '0'(main wired controller).
○
17 TIMER QUERY button
Press the button can inquire the timer setting information, such as the week, the setting operation mode, the
starting period, the end period and the setting temperature and so on.
○
18 TIMER SWITCH button
Содержание MGBT-F120W/PN1
Страница 28: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 29 60kW module ...
Страница 29: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 30 120kW module ...
Страница 30: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 31 180kW module ...
Страница 32: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 33 60kW module ...
Страница 33: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 34 120kW module ...
Страница 34: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 35 180kW module ...
Страница 36: ......
Страница 45: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 46 10 Exploded view 10 1 MGCT F30W PN1 ...
Страница 46: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 47 ...
Страница 48: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 49 MGCT D30W PN1 ...
Страница 49: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 50 ...
Страница 51: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 52 10 2 MGBT F60W PN1 ...
Страница 54: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 55 ...
Страница 55: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 56 ...
Страница 57: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 58 10 4 MGBT F180W PN1 ...
Страница 82: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 83 ...