34
When T2 is getting lower,
TE4<T2<TE3,the indoor fan will run at low speed.
T2<TE4, the indoor fan will shut off.
TE2
T2
TE1
Setting
Off
TE3
TE4
Low
While TE1=30, TE2=35, TE3=32, TE4=26
8.2.3 Defrost (only available to heating mode)
8.2.3.1
Condition of defrosting:
The units run with T3
<
-2
℃
for 40 minutes
8.2.3.2 Defrosting Action: