According to the capacity demand, the compressor will run at the corresponding frequency.
8.2.2.3 Indoor Fan Action
Anytime remote switchover for fan speed among high/low/auto, anti-cold air function takes
priority.
Auto fan in heating mode
8.2.2.4 Outdoor fan
In low temp. cooling zone, the outdoor fan will be controlled as below:
8.2.2.5 Anti-cold air:
When evaporator coil temp.T2 is getting higher,
T2>TE2, the indoor fan will run at setting speed.
TE1<T2<TE2, the indoor fan will run at low speed.