Air 
Evacuation

Air Evacuation

Safety Precautions

 CAUTION

• Use a vacuum pump with a gauge reading 

lower than -0.1MPa and an air discharge 
capacity above 40L/min.

• The outdoor unit does not need to be 

vacuumed. 

DO NOT

 open the outdoor 

unit’s gas and liquid stop valves.

•  Ensure that the Compound Meter reads 

-0.1MPa or below after 2 hours. If after 
three hours the gauge reading is still above 
-0.1MPa, check if there is a gas leak or 
water inside the pipe. If there is no leak,
perform another evacuation for 1 or 2 hours.  

• 

DO NOT 

use refrigerant gas to evacuate the 

system. 

 

Evacuation Instructions

Before using a manifold gauge and a vacuum 
pump, read their operation manuals to make 
sure you know how to use them properly.

Manifold Gauge

Compound gauge

-76cmHg

Low pressure valve

High pressure valve

Charge hose

Charge hose

Vacuum pump

Pressure gauge

Low pressure valve

Fig. 9.1

1.

 

Connect the manifold gauge’s charge hose to 
the service port on the outdoor unit’s low 
pressure valve.

2.

 

Connect the manifold gauge’s charge hose 
from the to the vacuum pump.

3.

 

Open the Low Pressure side of the manifold 
gauge. Keep the High Pressure side closed.

4.

 

Turn on the vacuum pump to evacuate the 
system.

5.

 

Run the vacuum for at least 15 minutes, or 
until the Compound Meter reads -76cmHG 
(-1x105Pa). 

6.

 

Close the manifold gauge’s Low Pressure valve 
and turn off the vacuum pump.

7.

 

Wait for 5 minutes, then check that there has 
been no change in system pressure. 

NOTE:

 If there is no change in system pressure, 

unscrew the cap from the packed valve (high 
pressure valve). If there is a change in system 
pressure, there may be a gas leak.   

8.

 

Insert hexagonal wrench into the packed valve 
(high pressure valve) and open the valve by 
turning the wrench 1/4 counterclockwise. 
Listen for gas to exit the system, then close the 
valve after 5 seconds. 

Flare nut

Cap

Valve body

Valve stem

Fig. 9.2

9.

 

Watch the Pressure Gauge for one minute to 
make sure that there is no change in pressure. It 
should read slightly higher than the atmospheric 
pressure.

10.

 

Remove the charge hose from the service port.

11.

 

Using hexagonal wrench, fully open both the 
high pressure and low pressure valves. 

OPEN VALVE STEMS GENTLY

When opening the valve stems, turn the hexagonal 
wrench until it hits against the stopper. 

DO NOT 

try to force the valve to open further.   

12.

 

Tighten valve caps by hand, then tighten it 
using the proper tool. 

9

Содержание MFAU-12FNXD0

Страница 1: ...TIONER Installation Manual Floor Standing Type IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future referenc...

Страница 2: ...tdoor Unit Installation 12 Outdoor Unit Installation Instructions 12 Outdoor Unit Types and Specifications 13 Notes on Drilling Hole in Wall 14 Drainpipe Installation 15 Table of Contents Installation...

Страница 3: ...Length and Elevation 17 Refrigerant Piping Connection Instructions 18 Wiring 20 Outdoor Unit Wiring 20 Indoor Unit Wiring 21 Power Specifications 22 Air Evacuation 23 Evacuation Instructions 23 Note o...

Страница 4: ...ometimes the pipe connections need a transfer connector installed on the outdoor unit Transfer connector 9 52 12 7 Packed with the indoor unit used for multi type models only NOTE Pipe size may differ...

Страница 5: ...ong winds typhoons and earthquakes that might affect your unit and locate it accordingly Failure to do so could cause the equipment to fail After installation ensure there are no refrigerant leaks and...

Страница 6: ...2 3 4 5 MC MC 6 7 Install the indoor unit Page 7 INSTALLATION ORDER Install the outdoor unit Page 13 Install the drainpipe Page 15 Evacuate the refrigeration system Page 23 Connect the wires Page 20...

Страница 7: ...y room as excessive moisture can short the unit and corrode the wiring CAUTION Install the indoor and outdoor units cables and wires at least 1m 3 2 from televisions or radios to prevent static or ima...

Страница 8: ...re room There is no direct radiation from heaters CAUTION DO NOT install the unit in the following Areas with oil drilling or fracking Coastal areas with high salt content in the air Areas with causti...

Страница 9: ...Page 9 Indoor Unit Installation Fig 4 3 195mm Hook 700mm 210mm 600mm...

Страница 10: ...the main body Fig 4 4 Fig 4 5 Affix the hook with a tapping screw onto the wall 195mm Hook Tapping screw Washer 6mm Hang the indoor unit on the hook The bottom of body can touch the floor or remain s...

Страница 11: ...rd until they click 3 Remove the face plate Remove the four screws See Fig 4 7 Open the bottom of the face plate at a 30 degree angle Lift the top of the face plate See Fig 4 8 Remove the string Allow...

Страница 12: ...door unit may not exceed the maximum allowable pipe length If possible DO NOT install the unit where it is exposed to direct sunlight If possible make sure the unit is located far away from your neigh...

Страница 13: ...21 85x11 8 487 19 2 298 11 7 800x554x333 31 5x21 8x13 1 514 20 24 340 13 39 Outdoor Unit Types and Specifications NOTE The minimum distance between the outdoor unit and walls described in the installa...

Страница 14: ...nstallation If the drain joint comes with a rubber seal see Fig 5 9 A do the following 1 Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit NOTE Make sure the wate...

Страница 15: ...rea to avoid water damage and slippage DO NOT pull the drainpipe forcefully This could disconnect it NOTE ON PURCHASING PIPES Installation requires a polyethylene tube exterior diameter 3 7 3 9cm inte...

Страница 16: ...Outdoor 12mm 0 5 inch Fig 6 4 NOTE When drilling the hole make sure to avoid wires plumbing and other sensitive components 4 Pass the drain hose through the wall hole Make sure the water drains to a s...

Страница 17: ...n the refrigeration cycle explosion or injury Ventilate the area immediately if there is refrigerant leakage during the installation Leaked refrigerant gas is both toxic and flammable Ensure there is...

Страница 18: ...ipe is cut at a perfect 90 angle Refer to Fig 7 1 for examples of bad cuts Oblique Rough Warped 90 Fig 7 1 Step 2 Remove burrs Burrs can affect the air tight seal of refrigerant piping connection They...

Страница 19: ...nder tightening may lead to leakage NOTE ON MINIMUM BEND RADIUS Carefully bend the tubing in the middle according to the diagram below DO NOT bend the tubing more than 90 or more than 3 times Bend the...

Страница 20: ...made through a switch that disconnects all poles with contact gap of at least 3mm 0 118 DO NOT modify the length of the power cord or use an extension cord CAUTION Connect the outdoor wires before co...

Страница 21: ...nal cable to reveal about 15cm 5 9 of the wire b Strip the insulation from the ends of the wires c Using a wire crimper crimp the u lugs to the ends of the wires Page 21 Wiring 2 Rotate the sensor dev...

Страница 22: ...Phase FREQUENCY AND VOLT 220 240V 50Hz 60Hz 220 240V 50Hz 60Hz CIRCUIT BREAKER FUSE A 20 16 20 16 INDOOR UNIT POWER WIRING mm 3x1 0 OUTDOOR UNIT POWER WIRING GROUND WIRING STRONG ELECTRIC SIGNAL WEAK...

Страница 23: ...the manifold gauge Keep the High Pressure side closed 4 Turn on the vacuum pump to evacuate the system 5 Run the vacuum for at least 15 minutes or until the Compound Meter reads 76cmHG 1x105Pa 6 Close...

Страница 24: ...rant containers must be opened slowly Always use protective gear when charging the system DO NOT mix refrigerants types Some systems require additional charging depending on pipe lengths The standard...

Страница 25: ...correctly d Ensure the indicators on the remote control and the display panel on the indoor unit work properly e Ensure the manual buttons on the indoor unit works properly f Check to see that the dra...

Страница 26: ...ct improvement Consult with the sales agency or manufacturer for details Please check the applicable models F GAS and manufacturer information from the Owner s Manual Product Fiche in the packaging of...

Отзывы: