Refrigerant Piping Connection

Safety Precautions

 WARNING

•  All field piping must be completed by a 

 

 

 

licensed technician and must comply with 
the local and national regulations. 

•  When the air conditioner is installed in a 

 

small room, measures must be taken to 
prevent the refrigerant concentration in 
the room from exceeding the safety limit 
in the event of refrigerant leakage. If the 
refrigerant leaks and its concentration 
exceeds its proper limit, hazards due to 
lack of oxygen may result.     

•  When installing the refrigeration system, 

 

 

 

ensure that air, dust, moisture or foreign 
substances do not enter the refrigerant 
circuit. Contamination in the system may 
cause poor operating capacity, high 
pressure in the refrigeration cycle, 
explosion or injury.     

 

•  Ventilate the area immediately if there is

 

   

refrigerant leakage during the installation. 
Leaked refrigerant gas is both toxic and 
flammable. Ensure there is no refrigerant 
leakage after completing the installation 
work.    

Notes On Pipe Length and Elevation

 

 

Ensure that the length of the refrigerant pipe, the 
number of bends, and the drop height between 
the indoor and outdoor units meets the 
requirements shown in Table 7.1:  

Table 7.1: The Maximum Length And Drop 

Height Based on Models. (Unit: m/ft.) 

Type of model

Capacity
 (Btu/h)

Length of 

piping

Maximum drop 

height

 

  North America, 
Australia

 

and the 

  eu frequency 
conversion Split 
            Type

<15K

25/82

10/32.8

15K - <24K

30/98.4

20/65.6

24K - <36K

50/164

25/82

36K - 

60K 

65/213

30/98.4

Other Split Type

12K

15/49

8/26

18K-24K

25/82

15/49

30K-36K

30/98.4

20/65.6

42K-60K

50/164

30/98.4

 Page 17

7

 Refrigerant Piping 

       Connection

 

Содержание MFAU-12FNXD0

Страница 1: ...TIONER Installation Manual Floor Standing Type IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future referenc...

Страница 2: ...tdoor Unit Installation 12 Outdoor Unit Installation Instructions 12 Outdoor Unit Types and Specifications 13 Notes on Drilling Hole in Wall 14 Drainpipe Installation 15 Table of Contents Installation...

Страница 3: ...Length and Elevation 17 Refrigerant Piping Connection Instructions 18 Wiring 20 Outdoor Unit Wiring 20 Indoor Unit Wiring 21 Power Specifications 22 Air Evacuation 23 Evacuation Instructions 23 Note o...

Страница 4: ...ometimes the pipe connections need a transfer connector installed on the outdoor unit Transfer connector 9 52 12 7 Packed with the indoor unit used for multi type models only NOTE Pipe size may differ...

Страница 5: ...ong winds typhoons and earthquakes that might affect your unit and locate it accordingly Failure to do so could cause the equipment to fail After installation ensure there are no refrigerant leaks and...

Страница 6: ...2 3 4 5 MC MC 6 7 Install the indoor unit Page 7 INSTALLATION ORDER Install the outdoor unit Page 13 Install the drainpipe Page 15 Evacuate the refrigeration system Page 23 Connect the wires Page 20...

Страница 7: ...y room as excessive moisture can short the unit and corrode the wiring CAUTION Install the indoor and outdoor units cables and wires at least 1m 3 2 from televisions or radios to prevent static or ima...

Страница 8: ...re room There is no direct radiation from heaters CAUTION DO NOT install the unit in the following Areas with oil drilling or fracking Coastal areas with high salt content in the air Areas with causti...

Страница 9: ...Page 9 Indoor Unit Installation Fig 4 3 195mm Hook 700mm 210mm 600mm...

Страница 10: ...the main body Fig 4 4 Fig 4 5 Affix the hook with a tapping screw onto the wall 195mm Hook Tapping screw Washer 6mm Hang the indoor unit on the hook The bottom of body can touch the floor or remain s...

Страница 11: ...rd until they click 3 Remove the face plate Remove the four screws See Fig 4 7 Open the bottom of the face plate at a 30 degree angle Lift the top of the face plate See Fig 4 8 Remove the string Allow...

Страница 12: ...door unit may not exceed the maximum allowable pipe length If possible DO NOT install the unit where it is exposed to direct sunlight If possible make sure the unit is located far away from your neigh...

Страница 13: ...21 85x11 8 487 19 2 298 11 7 800x554x333 31 5x21 8x13 1 514 20 24 340 13 39 Outdoor Unit Types and Specifications NOTE The minimum distance between the outdoor unit and walls described in the installa...

Страница 14: ...nstallation If the drain joint comes with a rubber seal see Fig 5 9 A do the following 1 Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit NOTE Make sure the wate...

Страница 15: ...rea to avoid water damage and slippage DO NOT pull the drainpipe forcefully This could disconnect it NOTE ON PURCHASING PIPES Installation requires a polyethylene tube exterior diameter 3 7 3 9cm inte...

Страница 16: ...Outdoor 12mm 0 5 inch Fig 6 4 NOTE When drilling the hole make sure to avoid wires plumbing and other sensitive components 4 Pass the drain hose through the wall hole Make sure the water drains to a s...

Страница 17: ...n the refrigeration cycle explosion or injury Ventilate the area immediately if there is refrigerant leakage during the installation Leaked refrigerant gas is both toxic and flammable Ensure there is...

Страница 18: ...ipe is cut at a perfect 90 angle Refer to Fig 7 1 for examples of bad cuts Oblique Rough Warped 90 Fig 7 1 Step 2 Remove burrs Burrs can affect the air tight seal of refrigerant piping connection They...

Страница 19: ...nder tightening may lead to leakage NOTE ON MINIMUM BEND RADIUS Carefully bend the tubing in the middle according to the diagram below DO NOT bend the tubing more than 90 or more than 3 times Bend the...

Страница 20: ...made through a switch that disconnects all poles with contact gap of at least 3mm 0 118 DO NOT modify the length of the power cord or use an extension cord CAUTION Connect the outdoor wires before co...

Страница 21: ...nal cable to reveal about 15cm 5 9 of the wire b Strip the insulation from the ends of the wires c Using a wire crimper crimp the u lugs to the ends of the wires Page 21 Wiring 2 Rotate the sensor dev...

Страница 22: ...Phase FREQUENCY AND VOLT 220 240V 50Hz 60Hz 220 240V 50Hz 60Hz CIRCUIT BREAKER FUSE A 20 16 20 16 INDOOR UNIT POWER WIRING mm 3x1 0 OUTDOOR UNIT POWER WIRING GROUND WIRING STRONG ELECTRIC SIGNAL WEAK...

Страница 23: ...the manifold gauge Keep the High Pressure side closed 4 Turn on the vacuum pump to evacuate the system 5 Run the vacuum for at least 15 minutes or until the Compound Meter reads 76cmHG 1x105Pa 6 Close...

Страница 24: ...rant containers must be opened slowly Always use protective gear when charging the system DO NOT mix refrigerants types Some systems require additional charging depending on pipe lengths The standard...

Страница 25: ...correctly d Ensure the indicators on the remote control and the display panel on the indoor unit work properly e Ensure the manual buttons on the indoor unit works properly f Check to see that the dra...

Страница 26: ...ct improvement Consult with the sales agency or manufacturer for details Please check the applicable models F GAS and manufacturer information from the Owner s Manual Product Fiche in the packaging of...

Отзывы: