6. Place flaring tool onto the form.
7. Turn the handle of the flaring tool 

clockwise until the pipe is fully flared. Flare 
the pipe in accordance with the dimensions 
shown in table 7.2.  

Table 7.2: PIPING EXTENSION BEYOND FLARE 
                 FORM

8. Remove the flaring tool and flare form, 

then inspect the end of the pipe for cracks 
and even flaring.  

Step 4: Connect pipes

Connect the copper pipes to the indoor unit first, 
then connect it to the outdoor unit. You should 
first connect the low-pressure pipe, then the high-
pressure pipe.  

1.

 

When connecting the flare nuts, apply a 
thin coat of refrigeration oil to the flared 
ends of the pipes.  

2.

 

Align the center of the two pipes that you 
will connect.  

Indoor unit tubing

Flare nut

Pipe

Fig. 7.6

3.

 

Tighten the flare nut as tightly as possible 
by hand. 

4.

 

Using a spanner, grip the nut on the unit 
tubing.

5. While firmly gripping the nut, use a torque 

wrench to tighten the flare nut according 
to the torque values in table 7.2.  

NOTE: 

Use both a spanner and a torque wrench 

when connecting or disconnecting pipes to/from 
the unit.

 

Fig. 7.7

 CAUTION

• 

Ensure to wrap insulation around the piping. 
Direct contact with the bare piping may result 
in burns or frostbite.  

• 

Make sure the pipe is properly connected. 
Over tightening may damage the bell mouth 
and under tightening may lead to leakage.   

NOTE ON MINIMUM BEND RADIUS

Carefully bend the tubing in the middle 
according to the diagram below. 

DO NOT 

bend 

the tubing more than 90° or more than 3 times.  

 

Bend the pipe with thumb

min-radius 10cm (3.9”)

Fig. 7.8

6.

 

After connecting the copper pipes to the 
indoor unit, wrap the power cable, signal 
cable and the piping together with 
binding tape.  

NOTE: DO NOT 

intertwine signal cable with 

other wires. While bundling these items 
together, do not intertwine or cross the signal 
cable with any other wiring. 

 

7. Thread this pipeline through the wall and 

connect it to the outdoor unit.  

8. Insulate all the piping, including the valves 

of the outdoor unit.  

9. Open the stop valves of the outdoor unit 

to start the flow of the refrigerant between 
the indoor and outdoor unit.  

 CAUTION

Check to make sure there is no refrigerant leak 
after completing the installation work. If there is 
a refrigerant leak, ventilate the area immediately 
and evacuate the system (refer to the Air 
Evacuation section of this manual).    

 Page 19 

Refrigerant Piping 

Connection

  Pipe 
gauge 

Tightening 

torque

Flare dimension (A) 

(Unit: mm/Inch)

Flare shape

Min.

Max.

Ø 6.4

18-20 N.m 
(183-204 kgf.cm)

8.4/0.33

8.7/0.34

R0.4~0.

45

°±

2

90

°     

±

4

A

Fig. 7.6

Ø 9.5

25-26 N.m 
(255-265 kgf.cm)

13.2/0.52

13.5/0.53

Ø 12.7

35-36 N.m 
(357-367 kgf.cm)

16.2/0.64

16.5/0.65

Ø 15.9

45-47 N.m 
(459-480 kgf.cm)

19.2/0.76

19.7/0.78

Ø 19.1

65-67 N.m 
(663-683kgf.cm)

23.2/0.91

23.7/0.93

Ø 22

75-85 N.m 
(765-867kgf.cm)

26.4/1.04

26.9/1.06

Содержание MFAU-12FNXD0

Страница 1: ...TIONER Installation Manual Floor Standing Type IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future referenc...

Страница 2: ...tdoor Unit Installation 12 Outdoor Unit Installation Instructions 12 Outdoor Unit Types and Specifications 13 Notes on Drilling Hole in Wall 14 Drainpipe Installation 15 Table of Contents Installation...

Страница 3: ...Length and Elevation 17 Refrigerant Piping Connection Instructions 18 Wiring 20 Outdoor Unit Wiring 20 Indoor Unit Wiring 21 Power Specifications 22 Air Evacuation 23 Evacuation Instructions 23 Note o...

Страница 4: ...ometimes the pipe connections need a transfer connector installed on the outdoor unit Transfer connector 9 52 12 7 Packed with the indoor unit used for multi type models only NOTE Pipe size may differ...

Страница 5: ...ong winds typhoons and earthquakes that might affect your unit and locate it accordingly Failure to do so could cause the equipment to fail After installation ensure there are no refrigerant leaks and...

Страница 6: ...2 3 4 5 MC MC 6 7 Install the indoor unit Page 7 INSTALLATION ORDER Install the outdoor unit Page 13 Install the drainpipe Page 15 Evacuate the refrigeration system Page 23 Connect the wires Page 20...

Страница 7: ...y room as excessive moisture can short the unit and corrode the wiring CAUTION Install the indoor and outdoor units cables and wires at least 1m 3 2 from televisions or radios to prevent static or ima...

Страница 8: ...re room There is no direct radiation from heaters CAUTION DO NOT install the unit in the following Areas with oil drilling or fracking Coastal areas with high salt content in the air Areas with causti...

Страница 9: ...Page 9 Indoor Unit Installation Fig 4 3 195mm Hook 700mm 210mm 600mm...

Страница 10: ...the main body Fig 4 4 Fig 4 5 Affix the hook with a tapping screw onto the wall 195mm Hook Tapping screw Washer 6mm Hang the indoor unit on the hook The bottom of body can touch the floor or remain s...

Страница 11: ...rd until they click 3 Remove the face plate Remove the four screws See Fig 4 7 Open the bottom of the face plate at a 30 degree angle Lift the top of the face plate See Fig 4 8 Remove the string Allow...

Страница 12: ...door unit may not exceed the maximum allowable pipe length If possible DO NOT install the unit where it is exposed to direct sunlight If possible make sure the unit is located far away from your neigh...

Страница 13: ...21 85x11 8 487 19 2 298 11 7 800x554x333 31 5x21 8x13 1 514 20 24 340 13 39 Outdoor Unit Types and Specifications NOTE The minimum distance between the outdoor unit and walls described in the installa...

Страница 14: ...nstallation If the drain joint comes with a rubber seal see Fig 5 9 A do the following 1 Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit NOTE Make sure the wate...

Страница 15: ...rea to avoid water damage and slippage DO NOT pull the drainpipe forcefully This could disconnect it NOTE ON PURCHASING PIPES Installation requires a polyethylene tube exterior diameter 3 7 3 9cm inte...

Страница 16: ...Outdoor 12mm 0 5 inch Fig 6 4 NOTE When drilling the hole make sure to avoid wires plumbing and other sensitive components 4 Pass the drain hose through the wall hole Make sure the water drains to a s...

Страница 17: ...n the refrigeration cycle explosion or injury Ventilate the area immediately if there is refrigerant leakage during the installation Leaked refrigerant gas is both toxic and flammable Ensure there is...

Страница 18: ...ipe is cut at a perfect 90 angle Refer to Fig 7 1 for examples of bad cuts Oblique Rough Warped 90 Fig 7 1 Step 2 Remove burrs Burrs can affect the air tight seal of refrigerant piping connection They...

Страница 19: ...nder tightening may lead to leakage NOTE ON MINIMUM BEND RADIUS Carefully bend the tubing in the middle according to the diagram below DO NOT bend the tubing more than 90 or more than 3 times Bend the...

Страница 20: ...made through a switch that disconnects all poles with contact gap of at least 3mm 0 118 DO NOT modify the length of the power cord or use an extension cord CAUTION Connect the outdoor wires before co...

Страница 21: ...nal cable to reveal about 15cm 5 9 of the wire b Strip the insulation from the ends of the wires c Using a wire crimper crimp the u lugs to the ends of the wires Page 21 Wiring 2 Rotate the sensor dev...

Страница 22: ...Phase FREQUENCY AND VOLT 220 240V 50Hz 60Hz 220 240V 50Hz 60Hz CIRCUIT BREAKER FUSE A 20 16 20 16 INDOOR UNIT POWER WIRING mm 3x1 0 OUTDOOR UNIT POWER WIRING GROUND WIRING STRONG ELECTRIC SIGNAL WEAK...

Страница 23: ...the manifold gauge Keep the High Pressure side closed 4 Turn on the vacuum pump to evacuate the system 5 Run the vacuum for at least 15 minutes or until the Compound Meter reads 76cmHG 1x105Pa 6 Close...

Страница 24: ...rant containers must be opened slowly Always use protective gear when charging the system DO NOT mix refrigerants types Some systems require additional charging depending on pipe lengths The standard...

Страница 25: ...correctly d Ensure the indicators on the remote control and the display panel on the indoor unit work properly e Ensure the manual buttons on the indoor unit works properly f Check to see that the dra...

Страница 26: ...ct improvement Consult with the sales agency or manufacturer for details Please check the applicable models F GAS and manufacturer information from the Owner s Manual Product Fiche in the packaging of...

Отзывы: