Refrigerant Piping 

Connection

Refrigerant Piping Connection Instructions

 CAUTION

• 

The branching pipe must be installed 
horizontally. An angle of more than 10° may 
cause malfunction. 

• 

DO NOT 

install the connecting pipe until 

both indoor and outdoor units have been 
installed.

  

 

• 

Insulate both the gas and liquid piping to 
prevent water leakage. 

Step1: Cut pipes

When preparing refrigerant pipes, take extra 
care to cut and flare them properly. This will 
ensure efficient operation and minimize the 
need for future maintenance.   
1.

 

Measure the distance between the indoor 
and outdoor units. 

2.

 

Using a pipe cutter, cut the pipe a little 
longer than the measured distance. 

 CAUTION

DO NOT 

deform pipe while cutting. Be extra 

careful not to damage, dent, or deform the pipe 
while cutting. This will drastically reduce the 
heating efficiency of the unit. 

  

1.

 

Make sure that the pipe is cut at a perfect 
90° angle. Refer to Fig. 7.1 for examples of 
bad cuts. 

Oblique

Rough

Warped

90°

Fig. 7.1

Step 2: Remove burrs.

Burrs can affect the air-tight seal of refrigerant 
piping connection. They must be completely 
removed. 

1.

 

Hold the pipe at a downward angle to 
prevent burrs from falling into the pipe. 

2.

 

Using a reamer or deburring tool, remove 
all burrs from the cut section of the pipe. 

Pipe

Reamer

Point down

Fig. 7.2

Step 3: Flare pipe ends

Proper flaring is essential to achieve an airtight 
seal.

1.

 

After removing burrs from cut pipe, seal 
the ends with PVC tape to prevent foreign 
materials from entering the pipe. 

  

 

2.

 

Sheath the pipe with insulating material.

3.

 

Place flare nuts on both ends of pipe. 
Make sure they are facing in the right 
direction, because you can’t put them on 
or change their direction after flaring. 
See Fig. 7.3   

Flare nut

Copper pipe

Fig. 7.3

4. Remove PVC tape from ends of pipe when 

ready to perform flaring work.

5. Clamp flare form on the end of the pipe. 

The end of the pipe must extend beyond 
the flare form. 

Flare form

Pipe

Fig. 7.4

Содержание MFAU-12FNXD0

Страница 1: ...TIONER Installation Manual Floor Standing Type IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future referenc...

Страница 2: ...tdoor Unit Installation 12 Outdoor Unit Installation Instructions 12 Outdoor Unit Types and Specifications 13 Notes on Drilling Hole in Wall 14 Drainpipe Installation 15 Table of Contents Installation...

Страница 3: ...Length and Elevation 17 Refrigerant Piping Connection Instructions 18 Wiring 20 Outdoor Unit Wiring 20 Indoor Unit Wiring 21 Power Specifications 22 Air Evacuation 23 Evacuation Instructions 23 Note o...

Страница 4: ...ometimes the pipe connections need a transfer connector installed on the outdoor unit Transfer connector 9 52 12 7 Packed with the indoor unit used for multi type models only NOTE Pipe size may differ...

Страница 5: ...ong winds typhoons and earthquakes that might affect your unit and locate it accordingly Failure to do so could cause the equipment to fail After installation ensure there are no refrigerant leaks and...

Страница 6: ...2 3 4 5 MC MC 6 7 Install the indoor unit Page 7 INSTALLATION ORDER Install the outdoor unit Page 13 Install the drainpipe Page 15 Evacuate the refrigeration system Page 23 Connect the wires Page 20...

Страница 7: ...y room as excessive moisture can short the unit and corrode the wiring CAUTION Install the indoor and outdoor units cables and wires at least 1m 3 2 from televisions or radios to prevent static or ima...

Страница 8: ...re room There is no direct radiation from heaters CAUTION DO NOT install the unit in the following Areas with oil drilling or fracking Coastal areas with high salt content in the air Areas with causti...

Страница 9: ...Page 9 Indoor Unit Installation Fig 4 3 195mm Hook 700mm 210mm 600mm...

Страница 10: ...the main body Fig 4 4 Fig 4 5 Affix the hook with a tapping screw onto the wall 195mm Hook Tapping screw Washer 6mm Hang the indoor unit on the hook The bottom of body can touch the floor or remain s...

Страница 11: ...rd until they click 3 Remove the face plate Remove the four screws See Fig 4 7 Open the bottom of the face plate at a 30 degree angle Lift the top of the face plate See Fig 4 8 Remove the string Allow...

Страница 12: ...door unit may not exceed the maximum allowable pipe length If possible DO NOT install the unit where it is exposed to direct sunlight If possible make sure the unit is located far away from your neigh...

Страница 13: ...21 85x11 8 487 19 2 298 11 7 800x554x333 31 5x21 8x13 1 514 20 24 340 13 39 Outdoor Unit Types and Specifications NOTE The minimum distance between the outdoor unit and walls described in the installa...

Страница 14: ...nstallation If the drain joint comes with a rubber seal see Fig 5 9 A do the following 1 Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit NOTE Make sure the wate...

Страница 15: ...rea to avoid water damage and slippage DO NOT pull the drainpipe forcefully This could disconnect it NOTE ON PURCHASING PIPES Installation requires a polyethylene tube exterior diameter 3 7 3 9cm inte...

Страница 16: ...Outdoor 12mm 0 5 inch Fig 6 4 NOTE When drilling the hole make sure to avoid wires plumbing and other sensitive components 4 Pass the drain hose through the wall hole Make sure the water drains to a s...

Страница 17: ...n the refrigeration cycle explosion or injury Ventilate the area immediately if there is refrigerant leakage during the installation Leaked refrigerant gas is both toxic and flammable Ensure there is...

Страница 18: ...ipe is cut at a perfect 90 angle Refer to Fig 7 1 for examples of bad cuts Oblique Rough Warped 90 Fig 7 1 Step 2 Remove burrs Burrs can affect the air tight seal of refrigerant piping connection They...

Страница 19: ...nder tightening may lead to leakage NOTE ON MINIMUM BEND RADIUS Carefully bend the tubing in the middle according to the diagram below DO NOT bend the tubing more than 90 or more than 3 times Bend the...

Страница 20: ...made through a switch that disconnects all poles with contact gap of at least 3mm 0 118 DO NOT modify the length of the power cord or use an extension cord CAUTION Connect the outdoor wires before co...

Страница 21: ...nal cable to reveal about 15cm 5 9 of the wire b Strip the insulation from the ends of the wires c Using a wire crimper crimp the u lugs to the ends of the wires Page 21 Wiring 2 Rotate the sensor dev...

Страница 22: ...Phase FREQUENCY AND VOLT 220 240V 50Hz 60Hz 220 240V 50Hz 60Hz CIRCUIT BREAKER FUSE A 20 16 20 16 INDOOR UNIT POWER WIRING mm 3x1 0 OUTDOOR UNIT POWER WIRING GROUND WIRING STRONG ELECTRIC SIGNAL WEAK...

Страница 23: ...the manifold gauge Keep the High Pressure side closed 4 Turn on the vacuum pump to evacuate the system 5 Run the vacuum for at least 15 minutes or until the Compound Meter reads 76cmHG 1x105Pa 6 Close...

Страница 24: ...rant containers must be opened slowly Always use protective gear when charging the system DO NOT mix refrigerants types Some systems require additional charging depending on pipe lengths The standard...

Страница 25: ...correctly d Ensure the indicators on the remote control and the display panel on the indoor unit work properly e Ensure the manual buttons on the indoor unit works properly f Check to see that the dra...

Страница 26: ...ct improvement Consult with the sales agency or manufacturer for details Please check the applicable models F GAS and manufacturer information from the Owner s Manual Product Fiche in the packaging of...

Отзывы: