MCAC-UTSM-201707 Midea R410A T3 50Hz Top-discharge Series
74
7
1. Fixed model that diffuses air at a 360 angle.
2. The outline size should increase when the air volume is over
350CMH. (For above 303) i.e., when about 9 diffusers are required, the
outline size should increase.
3. The diffuser pipes should preferably have the same length after
branching, and the minimum length of the ventilation pipes is 5m.
8
1. Fixed model that diffuses air at a 360 angle.
2. The outline size should increase when the air volume is over
350CMH. (For above 303) i.e., when about 9 diffusers are required, the
outline size should increase.
3. Proper air speed: For air speed of over 2-3.5m/s, select other
diffusers (with great noise).
4. Install the diffuser pipe if it is necessary to install the model of over
3.5m/s.
5. For purpose of cooling-only model.
9
1 The lengthwise adjustable model which diffuses air at a 360 angle.
2. With the change of the cooling/heating air flow, the horizontal and
vertical distance of the fan can be adjusted (applicable to department
store and exhibition hall where the decorative effect is essential).
10
1. Low noise compared with other air outlets. Applicable to tall buildings
that require along distance of air conditioning.
2. Select the ventilation pipe connection caliber according to the
distance and the air speed.
3. Applicable to store height of over 5m (for design of tall store such as
temple, consult manufacturer).
11
1. The fan is the adjustable type which can change direction of air flow.
It is used for deluxe decoration.
2. The outline size should increase when the air flow is over 450CMH
(3 or 4 SOLT) when about 6 diffusers are required, the outline size
should increase.
3. If the proper air speed is 2.5-5m/s and actual air speed reaches over
5m/s, it is necessary to choose other diffusers (with higher noise
values).
Содержание MFA3T-96CRN1
Страница 15: ...MCAC UTSM 201707 Midea R410A T3 50Hz Top discharge Series 14 3 Service Space...
Страница 17: ...MCAC UTSM 201707 Midea R410A T3 50Hz Top discharge Series 16 5 Wiring Diagrams MTB1T 96CWN1 MHB1T 96CWN1...
Страница 18: ...Midea R410A T3 50Hz Top discharge Series MCAC UTSM 201707 17 MTB1T 96HWN1 MHB1T 96HWN1...
Страница 30: ...Midea R410A T3 50Hz Top discharge Series MCAC UTSM 201707 29 3 Dimensions Unit mm MFA3T 96C H RN1...
Страница 31: ...MCAC UTSM 201707 Midea R410A T3 50Hz Top discharge Series 30 4 Service Space...
Страница 33: ...MCAC UTSM 201707 Midea R410A T3 50Hz Top discharge Series 32 6 Wiring Diagrams MFA3T 96CRN1...
Страница 34: ...Midea R410A T3 50Hz Top discharge Series MCAC UTSM 201707 33 MFA3T 96HRN1...
Страница 44: ...Midea R410A T3 50Hz Top discharge Series MCAC UTSM 201707 43 2 Dimension Unit mm MOVTA 96C H N1 R...
Страница 46: ...Midea R410A T3 50Hz Top discharge Series MCAC UTSM 201707 45 4 Wiring Diagrams MOVTA 96CN1 R...