Midea R410A T3 50Hz Top-discharge Series MCAC-UTSM-201707
63
After this connection has cooled, remove the nitrogen source from the liquid fitting service
port.
Replace the Schrader core in the liquid and vapor valves.
Leak test all refrigerant piping connections including the service port flare caps to be sure
they are leak tight.
Do not over tighten
. (between 40 and 60 inch-lbs. maximum.)
Evacuate the vapor line, evaporator and the liquid line, to 500 microns or less.
Replace cap on service ports. Do not remove the flare caps from the service ports except
when necessary for servicing the system.
Release the refrigerant charge into the system. Open both the liquid and vapor valves by
removing the plunger cap and with a hex wrench back out counter-clockwise until valve
stem just touches the chamfered retaining wall.
Replace plunger cap finger tight, then tighten an additional 1/12 turn (1/ hex flat). Cap must
be replaced to prevent leaks.
Do not connect manifold gauges unless trouble is suspected. Approximately 3/4 ounce of
refrigerant will be lost each time a standard manifold gauge is connected.
Never attempt to repair any brazed connections while the system is under pressure. Personal
injury could result.
After the pipes between the indoor unit and the outdoor unit are connected, replenish
compressed nitrogen to perform airtight test.
The airtight test is performed by using the compressed nitrogen, 2.94MPa (30kg/cm
2
G).
Tighten the spool of the low pressure valve and high pressure valve before compressing the
nitrogen.
Compress the nitrogen at the air vent of the gas valve.
The gas value and liquid value are closed in the process of compressing the nitrogen.
Do not
use oxygen, flammable gas or toxic gas in the airtight test.
Vacuum
From the following table, select a method of expelling air.
Length of connective pipe
(Single pass)
Procedure of expelling air
Содержание MFA3T-96CRN1
Страница 15: ...MCAC UTSM 201707 Midea R410A T3 50Hz Top discharge Series 14 3 Service Space...
Страница 17: ...MCAC UTSM 201707 Midea R410A T3 50Hz Top discharge Series 16 5 Wiring Diagrams MTB1T 96CWN1 MHB1T 96CWN1...
Страница 18: ...Midea R410A T3 50Hz Top discharge Series MCAC UTSM 201707 17 MTB1T 96HWN1 MHB1T 96HWN1...
Страница 30: ...Midea R410A T3 50Hz Top discharge Series MCAC UTSM 201707 29 3 Dimensions Unit mm MFA3T 96C H RN1...
Страница 31: ...MCAC UTSM 201707 Midea R410A T3 50Hz Top discharge Series 30 4 Service Space...
Страница 33: ...MCAC UTSM 201707 Midea R410A T3 50Hz Top discharge Series 32 6 Wiring Diagrams MFA3T 96CRN1...
Страница 34: ...Midea R410A T3 50Hz Top discharge Series MCAC UTSM 201707 33 MFA3T 96HRN1...
Страница 44: ...Midea R410A T3 50Hz Top discharge Series MCAC UTSM 201707 43 2 Dimension Unit mm MOVTA 96C H N1 R...
Страница 46: ...Midea R410A T3 50Hz Top discharge Series MCAC UTSM 201707 45 4 Wiring Diagrams MOVTA 96CN1 R...