67
Total refrigerant quantity for 10HP = refrigerant replenishment quantity upon shipment
(11kg) + additional refrigerant replenishment corresponding to the pipe length.
Calculate out the indoor volume [B (m
3
)] (according to the minimum volume)
Calculate out the refrigerant density:
[A (kg)] / [B (m
3
)]
≤ Density threshold: 0.3kg/m
3
Measures against crossing of the refrigerant density threshold.
In order to keep the refrigerant density below the threshold value, please install a
mechanic ventilation device. (Perform ventilation often.)
In case frequent ventilation is impossible, please install the leakage detection alarm
device linked with the mechanical ventilation device.
Содержание MFA3T-96CRN1
Страница 15: ...MCAC UTSM 201707 Midea R410A T3 50Hz Top discharge Series 14 3 Service Space...
Страница 17: ...MCAC UTSM 201707 Midea R410A T3 50Hz Top discharge Series 16 5 Wiring Diagrams MTB1T 96CWN1 MHB1T 96CWN1...
Страница 18: ...Midea R410A T3 50Hz Top discharge Series MCAC UTSM 201707 17 MTB1T 96HWN1 MHB1T 96HWN1...
Страница 30: ...Midea R410A T3 50Hz Top discharge Series MCAC UTSM 201707 29 3 Dimensions Unit mm MFA3T 96C H RN1...
Страница 31: ...MCAC UTSM 201707 Midea R410A T3 50Hz Top discharge Series 30 4 Service Space...
Страница 33: ...MCAC UTSM 201707 Midea R410A T3 50Hz Top discharge Series 32 6 Wiring Diagrams MFA3T 96CRN1...
Страница 34: ...Midea R410A T3 50Hz Top discharge Series MCAC UTSM 201707 33 MFA3T 96HRN1...
Страница 44: ...Midea R410A T3 50Hz Top discharge Series MCAC UTSM 201707 43 2 Dimension Unit mm MOVTA 96C H N1 R...
Страница 46: ...Midea R410A T3 50Hz Top discharge Series MCAC UTSM 201707 45 4 Wiring Diagrams MOVTA 96CN1 R...