3
3. The CCM and outdoor units, PC and
CCM adopt main-auxiliary responsion
communication. In the network of CCM
and outdoor units, CCM is the main unit
and outdoor units are the auxiliary units.
3. BASIC REQUIREMENTS
1. Applicable Power Voltage Range:
Input Voltage 220~240VAC.
2. AC Input Power Frequency:
50Hz/60Hz.
3. Working Ambient Temp.:
-15°C(-5°F)~ +43°C(+109°F).
4. Working Ambient Humidity: RH40%~
RH90%.
4. OPERATION
4-1 Key Words and Basic Functions
Power on or restore
After the CCM is power on or restore,
first all display segment on LCD will be
on and last 3 seconds, then all will be
off. 2 second later, the system enters
into normal display state, the CCM is in
the main page and display the data in
the first page.
Network Area Address Setting
The PC or gateway can connect max. 16
sets CCM. Every CCM can be viewed as
one network area and be distinguished
by address set through the address
setting button in keyboard. The setting
range is 16-31.
Address setting method:
pressing the Address set button
repeatedly, the address will be increased
one by one. When the address is equal
MAX.31 and you press once more, the
address will restart from 16.
Indicator Display
Indicator lamp will be on when the CCM
is power on.
CCM LOCKED
All the other button will not be on
controlled anytime when pushing the
CCM is locked, and unlock happens
when receiving the lock!