22
average, the outdoor gives the following
modification commands:
---- If the T2B
>
average, the relevant valve
needs to open 16p more
---- If the T2B= average, the relevant valve’s
open range remains as is
---- If the T2B
<
average, the relevant valve
needs to close 16p more
This modification is carried out every 2
minutes.
6.4.4.2 Heating Mode
The initial open angle of the EXV depends on
the size of the indoor model. The adjustment
range is 150-350p.
When the unit has been running for 3
minutes, the outdoor unit receives the indoor
units' indoor units' capacity demand and T2
information and then calculates their average.
After comparing each indoor unit’s T2 with
the average, the outdoor gives the following
modification commands:
----If the T2
>
2, the relevant valve
needs to close 16p more
---- If 2≥the T2≥ average-2, the
relevant valve’s open range remains as is
----If the T2
<
average-2, the relevant valve
needs to open 16p more
This modification is carried out every 2
minutes.
6.4.5 Four-Way Valve Control
In heating mode, a four-way valve is opened.
In defrosting, a four-way valve operates
according to the current defrosting action.
In other modes, a four-way valve is closed.
When the unit is switched from heating to
other modes, the four-way valve turns off
after the compressor has been off for 2
consecutive minutes.
Failure or protection (excluding discharge
temperature protection and high/low
pressure protection) causes the four-way
valve to immediately shut down.
Содержание MCH2U-18PHH2
Страница 3: ...3 MCH4U 36PHH2 WD30 metal plate 118 MCH5U 48PHH2 WE30 metal plate 125...
Страница 23: ...23 7 Wiring Diagrams 7 1 Wiring diagram of 1 drive 2 outdoor MCH2U 18PHH2...
Страница 24: ...24 7 2 Wiring diagram of 1 drive 3 outdoor MCH3U 27PHH2...
Страница 25: ...25 7 3 Wiring diagram of 1 drive 4 outdoor MCH4U 36PHH2...
Страница 26: ...26 7 4 Wiring diagram of MCH5U 48PHH2...
Страница 31: ...31 PCB board of MCH5U 48PHH2...
Страница 32: ...32 IPM board of MCH5U 48PHH2...
Страница 44: ...44...
Страница 46: ...46 Operating Standby Pic 2 IPM for 2 zone 3 zone...
Страница 47: ...47 PIC3 Main board LED when power on and unit standby Pic 2 IPM for5 zone Power Standby Operating...
Страница 54: ...54 8 4 1 7 Over voltage or under voltage protection diagnosis and solution...
Страница 59: ...59...
Страница 61: ...61 Operating Standby Pic 2 IPM board for 2 zone 3 zone...
Страница 62: ...62 PIC3 Main board LED when power on and unit standby Pic 2 IPM for5 zone Power Standby Operating...
Страница 64: ...64...
Страница 68: ...68 IPM board for 2 zone 3 zone...
Страница 70: ...70 IPM board for 4 zone...
Страница 73: ...73 Two ports of the inductance Inductance...
Страница 76: ...76 Vs Vcc Vsp FG...
Страница 78: ...78...
Страница 79: ...79...
Страница 81: ...81...
Страница 82: ...82...
Страница 84: ...84...
Страница 85: ...85...
Страница 87: ...87...
Страница 98: ...98 6 EXV check Disconnect the connectors...
Страница 99: ...99 Resistance to EXV coil Color of lead wire Normal Value Red Blue About 50 Red Yellow Brown Orange Brown White...
Страница 100: ...100 Red Blue Red Yellow...
Страница 101: ...101 Brown Orange...
Страница 102: ...102 Brown White...
Страница 112: ...112 Screws of front panel Screws of right rear panel Screws of front panel...
Страница 120: ...120 Screws of front panel Screws of right rear panel Screws of front panel...