20
2) If the compressor cumulative running
time reaches 35 minutes and T3< TCDI2
and T3
+
T30SUBT3TWO
≦
T30.
3) If the compressor cumulative running
time reaches 40 minutes and T3< -24C for 3
minutes.
4) If the compressor cumulative running
time reaches 120 minutes and T3<-15
℃
.
Defrost Stop Conditions
If any one of the following conditions is
satisfied, defrosting ends and the unit
returns to normal heating mode:
----T3 rises above than TCDE1
℃
.
----T3 remains at TCDE2
℃
or above for 80
seconds.
----The machine runs for 10 consecutive
minutes in defrosting mode.
Defrosting Action
:
off
on
Cool-F9
10S
30S
TimeA
10S
4-way valve
defrosting
Defrosting over
compressor
Indoor fan
Outdoor fan
EXV open
frequency
Max 10 minutes
frequency
Compressor stops
off
Anti-cold control
off
480P
480P for 240s
Condition of ending defrosting:
If any one of following items is satisfied,
defrosting will stop and the machine will turn
to normal heating mode.
①
T3 > TempQuitDefrost_ADD
℃
;.
②
The defrosting time achieves 10min.
③
Turn to other modes or off.
6.4.3 Outdoor Fan Control
6.4.3.1 Cooling Mode
Under normal operating conditions, the
system chooses the running fan speed
according to the ambient temperature:
Outdoor temperature
℃
45
43
Supper high fan speed
28
26
High fan speed
25
23
Middle fan speed
22
20
Low fan speed
19
17
Supper low fan speed
10
9
Breeze fan speed
0
-1
F fan speed
-5
-6
G fan speed
-10
-11
H fan speed
I fan speed
When low ambient cooling is in effect::
Outdoor fan speed control logic (low
ambient cooling)
When T4
<
15
℃
(59
℉
) and T3 < 30
℃
(86
℉
), the unit enters into low ambient cooling
mode. The outdoor fan chooses a speed
according to T3.
When T3
≥
38
℃
(100.4
℉
) or when T4
≥
20
℃
(68
℉
), the outdoor fan chooses a speed
according to T4 again.
Содержание MCH2U-18PHH2
Страница 3: ...3 MCH4U 36PHH2 WD30 metal plate 118 MCH5U 48PHH2 WE30 metal plate 125...
Страница 23: ...23 7 Wiring Diagrams 7 1 Wiring diagram of 1 drive 2 outdoor MCH2U 18PHH2...
Страница 24: ...24 7 2 Wiring diagram of 1 drive 3 outdoor MCH3U 27PHH2...
Страница 25: ...25 7 3 Wiring diagram of 1 drive 4 outdoor MCH4U 36PHH2...
Страница 26: ...26 7 4 Wiring diagram of MCH5U 48PHH2...
Страница 31: ...31 PCB board of MCH5U 48PHH2...
Страница 32: ...32 IPM board of MCH5U 48PHH2...
Страница 44: ...44...
Страница 46: ...46 Operating Standby Pic 2 IPM for 2 zone 3 zone...
Страница 47: ...47 PIC3 Main board LED when power on and unit standby Pic 2 IPM for5 zone Power Standby Operating...
Страница 54: ...54 8 4 1 7 Over voltage or under voltage protection diagnosis and solution...
Страница 59: ...59...
Страница 61: ...61 Operating Standby Pic 2 IPM board for 2 zone 3 zone...
Страница 62: ...62 PIC3 Main board LED when power on and unit standby Pic 2 IPM for5 zone Power Standby Operating...
Страница 64: ...64...
Страница 68: ...68 IPM board for 2 zone 3 zone...
Страница 70: ...70 IPM board for 4 zone...
Страница 73: ...73 Two ports of the inductance Inductance...
Страница 76: ...76 Vs Vcc Vsp FG...
Страница 78: ...78...
Страница 79: ...79...
Страница 81: ...81...
Страница 82: ...82...
Страница 84: ...84...
Страница 85: ...85...
Страница 87: ...87...
Страница 98: ...98 6 EXV check Disconnect the connectors...
Страница 99: ...99 Resistance to EXV coil Color of lead wire Normal Value Red Blue About 50 Red Yellow Brown Orange Brown White...
Страница 100: ...100 Red Blue Red Yellow...
Страница 101: ...101 Brown Orange...
Страница 102: ...102 Brown White...
Страница 112: ...112 Screws of front panel Screws of right rear panel Screws of front panel...
Страница 120: ...120 Screws of front panel Screws of right rear panel Screws of front panel...