ODMI-1103-A
COOL_F9
ICOOLLMT5
COOL_F8
ICOOLLMT4
COOL_F7
ICOOLLMT3
COOL_F6
ICOOLLMT2
COOL_F5
ICOOLLMT1
If the current frequency is lower than COOL_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>ICOOL,the AC will display the failure for 30 seconds
and stop. The AC will restart 3 minutes later.
Heating mode:
Current
frequency
(
Hz
)
Current limit value
(
A
)
Frequency limit
HEAT_F16
IHEATLMT12
Decrease the frequecny to HEAT_F4 and run at
HEAT_F4 for 3 minutes.
After that,the frequency will be adjusted according to
the capacity demand and rise to the upper level every
3 minutes
(When
the
frequency>Heat_F4
via
capacity
demand).
HEAT_F15
IHEATLMT11
HEAT_F14
IHEATLMT10
HEAT_F13
IHEATLMT9
HEAT_F12
IHEATLMT8
HEAT_F11
IHEATLMT7
HEAT_F10
IHEATLMT6
HEAT_F9
IHEATLMT5
HEAT_F8
IHEATLMT4
HEAT_F7
IHEATLMT3
HEAT_F6
IHEATLMT2
HEAT_F5
IHEATLMT1
If the current frequency is lower than HEAT_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>IHEAT,the AC will display the failure for 30 seconds
and stop. The AC will restart 3 minutes later.
6.5.5 Indoor / outdoor units communication protection
If the indoor units can not receive the feedback signal from the outdoor units for 2 minutes,the AC will stop
and display the failure.
7.5.6 High condenser coil temp. protection.
When T3>65
for
℃
3 seconds, the compressor will stop while the indoor fan and outdoor fan will continue.
When T3<52
, the protection will release
℃
and the compressor will restart after 3 minutes.
7.5.7 Outdoor unit anti-freezing protection
When T2B<0
for 250 seconds
℃
,the indoor unit capacity demand will be zero and resume to normal when
T2B>10
.
℃
7.5.8 Oil return
Running rules:
Содержание M2OC-14HRDN1
Страница 6: ...ODMI 1103 A 4 Wiring Diagram 4 1 M2OC 14HRDN1 Q 4 2 M2OC 14HRDN1...
Страница 7: ...ODMI 1103 A 4 3 M2OC1 18HRDN1 Q M3OC1 21HRDN1 Q 4 4 M2OC 18HRDN1 M3OC 27HRDN1...
Страница 8: ...ODMI 1103 A 4 5 M3OC1 27HRDN1 Q M4OC 24HRDN1 Q 4 6 M4OC1 27HRDN1 Q M4OC 27HRDN1...
Страница 9: ...ODMI 1103 A 4 7 M4OC 36HRDN1 4 8 M5OA 36HRDN1 Q...
Страница 11: ...ODMI 1103 A 5 4 Refrigeration circuit drawing of inverter quintuple type...