ODMI-1103-A
7.4.6 Opening degree of electronic expansion valve:
Opening degree equals the display data times 8
7.5 Protection
7.5.1 Three minutes delay at restart for compressor.
7.5.2 Temperature protection of compressor discharge.
When the compressor discharge temp. is getting higher, the running frequency will be limited as below
rules:
----If 102
℃
<T5<115
, decrease the freq
℃
uency to the lower level every 2 minutes till to F1.
---If T5>115
℃
for 10 seconds, the compressor will stop and restart till T5<90
℃
.
7.5.3 Under voltage protection
VOLLIMT1
VOLTAGE
No limit
VOLLIMT2
VOLLIMT3
Off
VOLFRE2
VOLFRE1
VOLREL1
VOLREL2
VOLREL3
Mode
VOLLIMT1(V)
VOLLIMT2(V)
VOLLIMT3(V)
VOLREL1(V)
VOLREL2(V)
VOLREL3(V)
VOLFRE1(Hz)
VOLFRE2(Hz)
M2OC-14HRDN1
220
200
80
250
210
100
62
54
M2OC-14HRDN1-Q
220
200
80
250
210
100
62
54
M2OC-18HRDN1
230
200
80
260
210
100
62
54
M2OC1-18HRDN1-Q
230
200
120
260
210
135
62
54
M3OC1-21HRDN1-Q
245
220
80
265
240
100
78
45
M3OC-27HRDN1
245
220
80
265
240
100
78
45
M3OC1-27HRDN1-Q
245
220
120
265
240
135
78
45
M4OC-24HRDN1-Q
245
220
120
265
240
135
78
45
M4OC-27HRDN1
221
210
80
260
225
100
62
54
M4OC1-27HRDN1-Q
221
210
80
260
225
100
53
44
M4OC-36HRDN1-Q
200
185
80
210
195
100
54
42
For M5OA-36HRDN1-Q,
VOLT_RST1_ADD
VOLTAGE
No limit
VOLT_LTM1_ADD
VOLT_RST2_ADD
VOLT_LTM2_ADD
VOLT_LTM_FREQ1_ADD
VOLT_LTM_FREQ2_ADD
Содержание M2OC-14HRDN1
Страница 6: ...ODMI 1103 A 4 Wiring Diagram 4 1 M2OC 14HRDN1 Q 4 2 M2OC 14HRDN1...
Страница 7: ...ODMI 1103 A 4 3 M2OC1 18HRDN1 Q M3OC1 21HRDN1 Q 4 4 M2OC 18HRDN1 M3OC 27HRDN1...
Страница 8: ...ODMI 1103 A 4 5 M3OC1 27HRDN1 Q M4OC 24HRDN1 Q 4 6 M4OC1 27HRDN1 Q M4OC 27HRDN1...
Страница 9: ...ODMI 1103 A 4 7 M4OC 36HRDN1 4 8 M5OA 36HRDN1 Q...
Страница 11: ...ODMI 1103 A 5 4 Refrigeration circuit drawing of inverter quintuple type...