ODMI-1103-A
8.3.10 Inverter module protection
8.3.11 Condenser high-temperature protection
When outdoor pipe temp. is more than 65¡C, the unit will stop, and unit runs again when outdoor pipe
temp. less than 52¡C.
Is the outdoor pipe temp. more than 65¡C ?
Is the outdoor pipe temp sensor right according to the annex 1
Replace the outdoor main board
No
Yes
Replace the outdoor pipe temp sensor
No
Replace inverter compressor
Repair connector
If the problem comes to again, check wingding resistance of inverter compressor, is it right?
Replace the IPM board
Are the U,V,W connected to compressor and inverter module right?
Yes
No