Flooded type water cooled screw chiller (PCB Control)
MCAC-CTSM-2012-11
57
Troubleshooting:
No. Alarm Trouble
Description
Action
Reset Type
Possible Cause
1 Power
Failure
Protection
Phase sequence relay
switches OFF
Compressor can not work; The
compressor stop running
immediately
Reset manually on the touch screen
The power quality is poor, there may exist
phase inversion, lacking phase or phase
imbalance.
2
Compressor Motor Protection
Compressor motor
module switches OFF
Compressor can not work; The
compressor stop running
immediately
Power off the unit and re-up
electricity,reset manually on the
touch screen
1.The power of motor is poor, there may
exist phase inversion, lacking
phase,over-voltage,under-voltage
2. The motor overheat
3
Compressor Overload Protection
Excess current and
cumulate energy make
the thermal relay trip
The compressor stop running
immediately
Reset manually on the touch screen
1,The compressor continue running in bad
condition, over-current
2,The setting value of thermal relay too low
4 Contactor
Protection
The coil of contactor
does not suction
normally
The compressor stop running
immediately
Reset manually on the touch screen
1.The suction of the contactor is abnormal
when Y type switch to
△
type
2.The vibration during operation cause the
contact to loosen
5
Anti-freeze Protection
Anti-freeze switch OFF
The compressor stop running
immediately
Reset manually on the touch screen
1,The chilled water flow fall sharply, the water
temperature too low
2,Anti-freeze switch is damaged or wiring
connection is abnormal
6
Water Flow Fault
The water flow switch
continue disconnecting
more than 5s
1.Compressor can not work; The
compressor stop running
immediately
;
2.Chilled water flow failure:The
chilled water pump stop working
after 30s delay; Cooling water pump
and cooling tower shut down after
120s delay
3.Cooling water flow failure: The
cooling water pump and cooling
tower shut down after 30s delay;
chilled water pump stop working
after 180s delay.
Power off the unit and re-up
electricity,reset manually on the
touch screen
1,The water pump failure, the water flow too
small
2,Water flow switch failure or wrong wiring
connection