Flooded type water cooled screw chiller (PCB Control)
MCAC-CTSM-2012-11
17
the unit in balance. Install a shockproof foundation when necessary.
4) Vibration isolators are recommended for all roof mounted installations or wherever vibration
transmission is a consideration. Neoprene Isolation is optional, it is recommended for normal
installations and provides good performance in most applications for the least cost. Spring
isolator is level adjustable, spring and cage type isolators for mounting under the unit base rails.
1” nominal deflection may vary slightly by application.
Typical Isolation:
Foundation Dimensions
D
E+
50
0
E
E va p C e n tre L in e
C o n d C e n tre L in e
A
A
A -A
R u b b e r P a d
(
δ
1 5 ) 2 0 0 X 2 0 0
C h ille r L e g
S te e l B a s e P la te (
δ
1 0 ) 2 0 0 X 1 5 0
P ro v id e d b y u s e r
A n ch o r B o lt M 2 0 X 4 0 0
P ro vid e d b y u s e r
N u t M 2 0
P ro v id e d b y u se r
G a s ke t 2 0 0
P ro vid e d b y u s e r
10
0
30
0
45
°
1 5 0 X 1 5 0
40
0
G ro u t c o n cre te
a fte r ch ille r in p la c e
D + 5 0 0
F
B
R
L
F ro n t s id e o f c h ille r
A
B
D ra in d itch
Foundation Bolt Installation Dimension Table
Model
Dimension
LSBLG**/MCF
Flooded Screw Water Cooled Chiller
365 465 560 750 825 925 1120
1230 1500
A(mm)
3490 3490 3490 3490 4490 4490 4490 4490 4490
B(mm)
1950 1950 2050 2050 1950 1950 2100 2100 2100
D(mm)
2790 2790 2790 2790 3790 3790 3790 3790 3790
E(mm)
1250 1250 1350 1350 1250 1250 1400 1400 1400
Anchor Bolt
Chiller Leg
Rubber Pad
Steel Base Plate
Concrete Base