Flooded type water cooled screw chiller (PCB Control)
MCAC-CTSM-2012-11
46
[Communication Lines of PCB and Touch Screen]
1.2 Electrical Elements Parameters Settings Inspection
1) Inspect whether the compressor overload protection value, which shall not exceed the
maximum compressor permissible current value indicated in the nameplate on the compressor,
is set correctly. The compressor overload protection value generally equals to the set value of
heat relay multiplied by variable ratio of current inductor, which is (250/5)50 in the following
case.
2) Inspect whether the value of phase loss and reversal protection is set correctly. The
over-/under-voltage protection value shall be ±10% of the rated voltage.
1.3 Unit Parts and Inspection of Leak Points
1) The discharge line valve and suction line valve of the compressor must be fully open (turn
anticlockwise to open) and the cores shall be tightly locked to prevent leakage of refrigerant.
Protection setting of
compressor heat
relay overload value
The discharge line
valve and suction line
valve shall be open
(both valves in the
figure are closed, and
shall be opened
before start-up).
The discharge line
valve and suction line
valve shall be open
(both valves in the
figure are closed, and
shall be opened before
start-up).