Flooded type water cooled screw chiller (PCB Control)
MCAC-CTSM-2012-11
51
(6) Inspect whether the flow in the water pump meets the requirements of the unit.
(7) Inspect whether the power supply of the unit is stable.
2) Parameters Inspections during Start-up and Operation
(1) The maximum range of parameters for normal operation of R134a refrigerant unit
See table 2 for the maximum range of performance parameters of R134a refrigerant:
[Table 2]
(1) Keep good record of unit data during commissioning.
2. Maintenance and Service
ATTENTION:
1) All installation parts must be maintained by the personnel in charge, in order to avoid material
deterioration and injuries to people. Faults and leaks must be repaired immediately. The
authorized technician must have the responsibility to repair the fault immediately. Each time
repairs have been carried out to the unit, the operation of the safety devices must be re-checked.
2) Do not use oxygen to purge lines or to pressurize a machine for any purpose. Oxygen gas reacts
violently with oil, grease, and other common substances.
3) The necessary protection equipment must be available, and appropriate fire extinguishers for the
system and the refrigerant type used must be within easy reach.
4) Do not siphon refrigerant. Avoid spilling liquid refrigerant on skin or splashing it into the eyes. Use
safety goggles. Wash any spills from the skin with soap and water. If liquid refrigerant enters the
eyes, immediately and abundantly flush the eyes with water and consult a doctor.
5) Never let an open flame or live steam close to a refrigerant container. Dangerous overpressure
can result. If it is necessary to heat refrigerant, only use warm water.
6) Do not re-use disposable (non-returnable) cylinders or attempt to refill them. It is dangerous and
illegal. When cylinders are empty, evacuate the remaining gas pressure, and move the cylinders
to a place designated for their recovery. Do not incinerate.
7) Ensure that you are using the correct refrigerant type before recharging the unit.Charging any
refrigerant other than the original charge type (R-134a) will impair machine operation and can
even lead to a destruction of the compressors. The compressors operating with this refrigerant
type are lubricated with a synthetic
Working Condition
Refrigeration
Discharge temp.
℃
40~50
℃
Suction temp.
℃
5~9
℃
Suction super-heating degree
℃
1~3
℃
Discharge super-heating degree
℃
10~15
℃
Discharge pressure MPa
0.8~0.9MPa
Suction pressure MPa
0.2~0.25MPa