Situation 2: L0 or L4 error appears immediately after the compressor starts up
L0 / L4
U V W wire between inverter module and
compressor is not connected properly
1
Yes
Ensure U V W wire is connected properly
No
Inverter module is damaged
2
Yes
Replace the inverter module
3
No
Compressor has malfunctioned
4
Yes
Replace the compressor
No
Replace the outdoor unit main PCB
Notes:
1.
Connect the U V W wire from the inverter module to the correct compressor terminals, as indicated by the labels on the compressor.
2.
Measure the resistance between each of U, V and W and each of P and N on the inverter module. All the resistances should be infinite. If any of them are
not infinite, the inverter module is damaged and should be replaced. Refer to
Figure 4-2.5 to 4-2.7 in Part 4, 2.1 Main PCBs for Refrigerant System,
Inverter Module
3.
When replacing an inverter module, a layer of thermally conductive silica gel should be painted on the IPM module, IGBT, diode brigde rectifer (on the
reverse side of the inverter module PCB). Refer to Figure 4-4.2.
4.
The normal resistances of the inverter compressor are 0.7-
differ from these specifications, the compressor has malfunctioned.
Midea CAC Confidential
Содержание HB-A100/CGN8-B
Страница 1: ...M Thermal A Series Split Commercial Air Conditioners R32 Service Manual Midea CAC Confidential...
Страница 3: ...M thermal Split 2 202004 Midea M thermal Split Service Manual Midea CAC Confidential...
Страница 7: ...M thermal Split 6 202004 Midea M thermal Split Service Manual Midea CAC Confidential...
Страница 17: ...M thermal Split Midea M thermal Split Service Manual 16 202004 Midea CAC Confidential...