M thermal Split
202004 83
4.20 Inverter module Troubleshooting for single-phase models
Digital display output
4.20.1
Description
4.20.2
Inverter module protection.
M thermal Split stops running.
Specific error code L0, L1, L2, L4, L5, L8, L9 is displayed on the user interface and the main control board of refrigerant
system.
Possible causes
4.20.3
Inverter module protection.
DC bus low or high voltage protection.
MCE error(DC bus low or high voltage protection or software over current protection)
Zero speed protection.
Excessive compressor frequency variation.
Actual compressor frequency differs from target frequency.
High pressure protection.
PED board self checking fail.
Specific error codes for inverter module protection
4.20.4
Table 4-4.1: Specific error codes
Specific error code
Content
L0
Inverter module protection
L1
DC bus low voltage protection
L2
DC bus high voltage protection
L4
MCE error(DC bus low or high voltage protection or software over current protection)
L5
Zero speed protection
L8
Compressor frequency variation greater than 15Hz within 1 second protection
L9
Actual compressor frequency differs from target frequency by more than 15Hz protection
Midea CAC Confidential
Содержание HB-A100/CGN8-B
Страница 1: ...M Thermal A Series Split Commercial Air Conditioners R32 Service Manual Midea CAC Confidential...
Страница 3: ...M thermal Split 2 202004 Midea M thermal Split Service Manual Midea CAC Confidential...
Страница 7: ...M thermal Split 6 202004 Midea M thermal Split Service Manual Midea CAC Confidential...
Страница 17: ...M thermal Split Midea M thermal Split Service Manual 16 202004 Midea CAC Confidential...