M thermal Split
202004 61
Procedure
4.6.4
E5 / E6 / E9 / EA
Temperature sensor connection on
outdoor unit main PCB is loose
1
Yes
Ensure the sensor is connected properly
No
Temperature sensor has short-circuited
or failed
2
Yes
Replace the sensor
No
Replace outdoor unit main PCB
Notes:
1.
Air side heat exchanger refrigerant outlet temperature sensor and outdoor ambient temperature sensor connections are port CN9 on the
MHA-V4(6,8,10)W/D2N8-B outdoor unit refrigerant system main PCB (labeled 12 in Figure 4-2.2
Main PCBs for Refrigerant System, Inverter
Module
9 on the MHA-V12(14,16)W/D2N8-B outdoor unit refrigerant system main PCB (labeled 12 in Figure 4-2.3
Main PCBs for
Refrigerant System, Inverter Module , port CN9 on the MHA-V12(14,16)W/D2RN8-B outdoor unit refrigerant system main PCB (labeled 17 in Figure 4-2.4
Main PCBs for Refrigerant System, Inverter Module . Discharge pipe temperature sensor connection are port CN8 on the
MHA-V4(6,8,10)W/D2N8-B outdoor unit refrigerant system main PCB (labeled 15 in Figure 4-2.2
Main PCBs for Refrigerant System, Inverter
Module
8 on the MHA-V12(14,16)W/D2N8-B outdoor unit refrigerant system main PCB (labeled 15 in Figure 4-2.3
Main PCBs for
Refrigerant System, Inverter Module , port CN4 on the MHA-V12(14,16)W/D2RN8-B outdoor unit refrigerant system main PCB (labeled 15 in Figure 4-2.4
Main PCBs for Refrigerant System, Inverter Module . Suction pipe temperature sensor connection are port CN1 on the
MHA-V4(6,8,10)W/D2N8-B outdoor unit refrigerant system main PCB (labeled 14 in Figure 4-2.2
Main PCBs for Refrigerant System, Inverter
Module
1 on the MHA-V12(14,16)W/D2N8-B outdoor unit refrigerant system main PCB (labeled 14 in Figure 4-2.3
Main PCBs for
Refrigerant System, Inverter Module , port CN8 on the MHA-V12(14,16)W/D2RN8-B outdoor unit refrigerant system main PCB (labeled 16 in Figure 4-2.4
Main PCBs for Refrigerant System, Inverter Module .
2.
Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor s resistance
characteristics table, the sensor has failed. Refer to Table 4-5.1, and Table 4-5.2 in Part 4, 5.1
.
Midea CAC Confidential
Содержание HB-A100/CGN8-B
Страница 1: ...M Thermal A Series Split Commercial Air Conditioners R32 Service Manual Midea CAC Confidential...
Страница 3: ...M thermal Split 2 202004 Midea M thermal Split Service Manual Midea CAC Confidential...
Страница 7: ...M thermal Split 6 202004 Midea M thermal Split Service Manual Midea CAC Confidential...
Страница 17: ...M thermal Split Midea M thermal Split Service Manual 16 202004 Midea CAC Confidential...