2.4 Digital Display Output
Table 4-2.9: Digital display output in different operating states
M thermal Split system state
Parameters displayed on outdoor
unit main PCB DSP1
Parameters displayed on hydronic
box main PCB DSP1
On standby
0
0
Normal operation
Running speed of the compressor in
rotations per second
Leaving water temperature (°C)
Error or protection
Error or protection code
Error or protection code
2.5 DIP switch setting and Modbus function
(Modbus function will be available in 2020-5-30)
The rotating coded switch S3(0-F) on the main control board of hydraulic module is used for setting the modbus
address. By default the units have this coded switch positioned=0, but this corresponds to the modbus address 16, while
the others positions corresponds the number, e.g. pos=2 is address 2, pos=5 is address 5.
Figure 4-2.10: Rotating switch
Figure 4-2.11: Connection
Note: Wired controller is integrated in the hydronic box.
Figure 4-2.12: Wiring
Input Voltage(A/B)
13.5VAC
Wiring size
0.75mm²
Midea CAC Confidential