When relocate  the  unit to  another  place, perform evacuation using vacuum pump.

 Make sure the refrigerant added into the air conditioner is liquid form in any case.
(Not applicable to the units with R22 )

Open the valve stem until it hits against the stopper. Do not try to open it further.
Securely tighten the valve stem cap with aspanner or the like.
Valve stem cap tightening torque (See Tightening torque table in previous page ).

Outdoor
unit

Indoor
unit

Refrigerant 

Flare nut

Stopper

Cap

Valve body

Packed valve

Half union

Gas side

Liquid side

A

C

D

B

Valve stem

Fig.22

Fig.23

When Using the Vacuum Pump

(For method  of using a  manifold valve, refer to its operation manual.)
1. Completely tighten the flare nuts, A, B, C, D, connect the manifold valve charge
     hose to  a charge port of the low-pressure valve on the gas pipe side.
2. Connect the charge hose connection to the  vacuum pump.
3. Fully open the handle Lo of the manifold valve.
4. Operate the vacuum pump to evacuate. After starting evacuation, slightly loose the
     flare  nut of the Lo valve on the gas pipe side and check that the air is entering
     (Operation  noise of  the vacuum  pump changes  and  a  compound meter indicates
      0 instead of  minus)
5. After  the  evacuation is complete, fully close the 
    handle Lo of the manifold valve and  stop the 
    operation of the vacuum pump.
    Make evacuation  for  15  minutes or more and 
    check that the compound meter indicates
    -76cmHg  (-1x10 Pa).

o

6. Turn the stem of the packed valve B about 45  
    counterclockwise for 6~7 seconds after the gas 
    coming out, then tighten the flare nut again. Make 
    sure the pressure display in the pressure indicator 
    is a little higher than the atmosphere pressure.
7. Remove the charge hose from the Low pressure charge hose.
8. Fully open the packed valve stems B and A.
9. Securely tighten the cap of the packed valve.

Manifold valve

Compound meter

-76cmHg

Handle Lo

Handle Hi

Charge hose

Charge hose

Vacuum pump

Pressure gauge

Low pressure valve

Fig.24

   

Caution in handling the packed valve

5

12

 AIR PURGING

Содержание Elite Plus MSE18HRN1

Страница 1: ...please read this manual carefully and keep it for future reference ROOM AIR CONDITIONER Before using your air conditioner please read this manual carefully and keep it for future reference ROOM AIR CO...

Страница 2: ...authorised installer for installation of this unit The air conditioner is not intended for use by young children or infirmed persons without supervision Young children should be supervised to ensure t...

Страница 3: ...nd this installation instructions An independent circuit and single outlet must be used If electrical circuit capacity is not enough or defect found in electrical work it will cause electrical shock f...

Страница 4: ...e connection side right side should have more than 60cm of clearance Do not place animals and plants in the path of the air inlet or outlet Take the air conditioner weight into account and select a pl...

Страница 5: ...should be free from obstructions CAUTION 1 2 3 4 5 6 7 Parts you must purchase The minimum pipe wall thickness of 0 7mm is required 6 35 9 53 12 7 8 2 Self tapping Screw B ST2 9X10 Remote controller I...

Страница 6: ...ponding mounting points on the installation plate Dimensions are in mm unless otherwise stated 1 Determine hole positions according to the diagram detailed in Fig 5 Drill one 1 hole 65mm slanting slig...

Страница 7: ...oor unit from side to side to see that it is securely hooked 3 Piping can easily be made by lifting the indoor unit with a cushioning material between the indoor unit and the wall Get it out after fin...

Страница 8: ...n hose sloped downward to drain out the cond ensed water smoothly CAUTION Install the outdoor unit on a rigid base to prevent increasing noise level and vibration Determine the air outlet direction wh...

Страница 9: ...90 C Roughness Burr Main cause for refrigerant leakage is due to defect in the flaring work Carry out correct flaring work using the following procedure A Cut the pipes and the cable 1 Use the piping...

Страница 10: ...8 1 0 9 53 2940 300kgf cm 3430 350kgf cm Fig 19 Indoor unit tubing Flare nut Pipings Fig 18 Electric safety regulations for the initial Installation 1 If there is serious safety problem about the pow...

Страница 11: ...ft the indoor unit panel up remove the electrical box cover by loosening the screw 4 Ensure the colour of wires of outdoor unit and the terminal Nos are the same to the indoor s respectively 5 Wrap th...

Страница 12: ...onnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active phase conductors CAUTION CAUTION CAUTION CAUTION Air and m...

Страница 13: ...Lo of the manifold valve 4 Operate the vacuum pump to evacuate After starting evacuation slightly loose the flare nut of the Lo valve on the gas pipe side and check that the air is entering Operation...

Страница 14: ...t connection or outdoor unit connections by a soft brush to check for leakage of the connecting points of th piping If bubbles come out the pipes have leakage 2 Leak detector Use the leak detector to...

Страница 15: ...CS406 I1 2200018041...

Отзывы: