background image

Copyright 2020 CMNA

                                                           3300 Riverwood Parkway Atlanta GA 30339                                 32801002001

TROUBLESHOOTING

For ease of service, the systems are equipped with diagnostic code display LEDs on some outdoor units. The outdoor diagnostic display consists 
of two LEDs (red and green) on the outdoor unit board and is limited to a few errors. The indoor diagnostic display is a digital readout on the 
display panel. If possible, always check the diagnostic codes displayed on the indoor unit first before consulting a service technician. The 
diagnostic codes, displayed in the indoor and outdoor units, are listed in Table 19.

Table 19 — Indoor Unit Diagnostic Guides

For additional diagnostic information, refer to the indoor unit service manual. 

ADVANCED SERVICE AND INSTALLATION FUNCTIONS

Refer to the service manual of the Wireless Remote Controller for access to advanced function such as:
• Auto-Start Function
• Temperature Compensation
• Filter reminder
• Indoor Fan Motor Speed Control after set temperature is reached
• Lowest or Highest Temperature Setting
• Static Pressure Setting
All changes should be performed 

ONLY

 by authorized professionals.

RUNNING LED

TIMER LED

DISPLAY

ERROR INFORMATION

--

--

dF

Defrost

--

--

cF

Warming in heating mode

--

--

SC

Self clean

--

--

CL

Clean filter

--

--

nF

Replacing filter

--

--

FP

Heating in room temperature under 46°F(8°C)

--

--

FC

Forced cooling

--

--

AP

AP mode for WIFI setup

--

--

CP

Remote start stop contact is open

--

--

AF

Constant Air Flow

--

--

LL

Remote or Wire controller Lock 

--

--

d1

Receive DR1 signal

--

--

d2

Receive DR2 signal

--

--

d3

Receive DR3 signal

--

--

dE

DR input error signal

1 time

OFF

E0

Indoor unit EEPROM parameter error

2 times

OFF

E1

Indoor/outdoor unit communication error

4 times

OFF

E3

The indoor fan speed is operating outside of the normal range

5 times

OFF

E4

Indoor room temperature sensor T1 is in open circuit or has short circuited

6 times

OFF

E5

Evaporator coil middle temperature sensor T2 is in open circuit or has short circuited

7 times

OFF

EC

Refrigerant leakage detection

8 times

OFF

EE

Water-level alarm malfunction

9 times

OFF

E8

Communication error between master and slave unit (for twins system)

10 times

OFF

E9

Another indoor unit malfunction (for twins system)

11 times

OFF

Ed

Outdoor unit malfunction

1 time

ON

F0

Current overload protection

2 times

ON

F1

Outdoor room temperature sensor T4 is in open circuit or has short circuited

3 times

ON

F2

Condenser coil temperature sensor T3 is in open circuit or has short circuited

4 times

ON

F3

Compressor discharge temperature sensor TP is in open circuit or has short circuited

5 times

ON

F4

Outdoor unit EEPROM parameter error

6 times

ON

F5

The outdoor fan speed is operating outside of the normal range

7 times

ON

F6

Evaporator coil outlet temperature sensor T2B is in open circuit or has short circuited (for free-

match indoor units)

11 times

ON

FA

Communication error between indoor two chips 

1 time

FLASH

P0

IPM malfunction or IGBT over-strong current protection

2 times

FLASH

P1

Over voltage or over low voltage protection

3 times

FLASH

P2

Top temperature protection of compressor

5 times

FLASH

P4

Inverter compressor drive error

6 times

FLASH

--

Indoor units mode conflict (match with multi outdoor unit) 

7 times

FLASH

P6

Low pressure protection

8 times

FLASH

P7

IGBT temperature sensor TH is in open circuit or has short circuited

Содержание DLFLAA

Страница 1: ...work gloves Have a fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions included in the literature and attached to the unit Consult local building codes a...

Страница 2: ...allation parts and accessories to install the system Improper installation may result in water leakage electrical shock and fire or cause the equipment to fail Keep the installation manual in a safe p...

Страница 3: ...84 11 8 299 13 3 339 3 0 75 2 5 64 4 9 124 6 8 174 1 7 44 A HEIGHT 48 1 1222 C WIDTH 19 7 501 4 8 121 2 4 61 6 7 171 2 2 57 D DUCT 18 2 462 E DUCT 10 3 262 B DEPTH 21 1 535 0 8 21 0 5 13 0 6 16 18 4...

Страница 4: ...med according to the installation instructions Improper installation can cause water leakage electrical shock or fire In North America installation must be performed in accordance with the requirement...

Страница 5: ...t is installed over a finished ceiling and or living area building codes may require a field supplied secondary condensate pan to be installed under the entire unit Some localities may allow as an alt...

Страница 6: ...t 5 Install the drain lines Fig 7 Vertical Upflow Installations Fig 8 Horizontal Right Installations NOTE For a horizontal right installation secondary condensate pan field supplied must be installed...

Страница 7: ...d drain pan assembly 9 Reinstall the pipe temperature sensor in its original position Attach the room temperature sensor to the evaporator output pipe protection sleeve Fig 15 Reinstall the Pipe Tempe...

Страница 8: ...uipped with the electric auxiliary heat module please check the electric auxiliary heat module specification that is compatible with the unit to avoid unnecessary consequences caused by improper match...

Страница 9: ...into the opening made by removal of the sheet metal cover s Ensure the two support rod ends are on the opposite bulkhead Fig 24 Insert Heating Module 5 Use the 3 screws 6 screws for 15K or 20K remove...

Страница 10: ...quirements and local codes see Table 6 on page 11 Choose the power cord and the power cord installation location see Figure 30 Each circuit breaker group needs to connect to the power input line Where...

Страница 11: ...do not have a 90 degree elbow and 10ft 3m of main duct to first branch takeoff may require internal acoustical insulation lining As an alternative fibrous ductwork may be used if constructed and insta...

Страница 12: ...ood 2 Use a 2 5in 65mm core drill to drill a hole in the wall Make sure the hole is drilled at a slight downward angle so that the outdoor end of the hole is lower than the indoor end by about 0 5in 1...

Страница 13: ...g an airtight seal a After removing the burrs from the cut pipe seal the ends with PVC tape to prevent foreign materials from entering the pipe b Sheath the pipe with insulating material c Place flare...

Страница 14: ...nder to prevent kinking or damaging the tubing 6 After connecting the copper pipes to the outdoor unit wrap the power cable signal cable and the piping together with binding tape NOTE While bundling t...

Страница 15: ...ost positive way of assuring a system is free of air and moisture see Fig 49 NOTE DO NOT add a filter line drier Fig 49 Deep Vacuum Graph Triple Evacuation Method The triple evacuation method should b...

Страница 16: ...it would lose power A disconnect switch is not required on the indoor unit side on the wiring between the outdoor and indoor unit A 3 pole disconnect purchased separately may be used for extra protect...

Страница 17: ...e is a ground wire To minimize voltage drop the factory recommended wire size is 14 2 power stranded with a ground Communication Wiring A separate 2 wire cable stranded shielded copper conductor with...

Страница 18: ...0 5 0 20 120 36 5 0 42 250 48 5 0 65 400 3 S 1 L1 2 L2 208 230 1 60 Power Supply Main 1 L1 208 230 1 60 2 L2 3 S 1 L1 2 L2 CONNECTING CABLE OUTDOOR TO INDOOR Indoor Unit Power Supply 208 230 1 60 Indo...

Страница 19: ...Indoor Unit Control Box Sizes 36 48 LED Display The control displays active faults codes on the LED display When the control displays the fault code and the LED flashes quickly there is something wro...

Страница 20: ...nnected b Turn off the power to the indoor and outdoor units for 3 minutes c Turn the power back on Wait 1 minute and check the 24 volt Interface digital display If the display reads 00 then proceed I...

Страница 21: ...troller exits the MODIFICATION mode After you power OFF the unit power the unit ON again and the unit retains the setting value Fig 65 RG57 Remote Controller FP Activate Disable freeze protection func...

Страница 22: ...1 400 1 310 1 215 1 105 950 825 Low 1 525 1 450 1 372 1 280 1 190 1 074 935 785 650 36 SP1 High 1 335 1 270 1 165 1 062 950 810 645 450 240 Medium 1 185 1 100 990 845 685 520 335 Low 1 020 915 775 60...

Страница 23: ...Pressurein WC High Medium Low SP4 0 200 400 600 800 1 000 1 200 1 400 1 600 1 800 2 000 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Air ow CFM Sta cPressurein WC High Medium Low SP1 0 200 400 600 800 1 000 1...

Страница 24: ...M Sta cPressurein WC High Medium Low SP2 0 200 400 600 800 1 000 1 200 1 400 1 600 1 800 2 000 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Air ow CFM Sta c Pressurein WC High Medium Low SP3 0 200 400 600 800...

Страница 25: ...conditioner Turn off the main power switch and reinstall the test cover NOTE If the unit malfunctions or does not operate according to your expectations please refer to the Troubleshooting section of...

Страница 26: ...FF E0 Indoor unit EEPROM parameter error 2 times OFF E1 Indoor outdoor unit communication error 4 times OFF E3 The indoor fan speed is operating outside of the normal range 5 times OFF E4 Indoor room...

Отзывы: