background image

4                                                                 

Specifications subject to change without notice.                                                                         32801002001

INSTALLATION REQUIREMENTS

Review the following information before installing the unit: 
• Do not install the indoor units near a direct source of heat such as 

direct sunlight or a heating appliance.

• Allow sufficient space for airflow and unit servicing. See Fig. 6 for 

the minimum required distances between the unit and the walls or 

ceilings.

• Communication wiring must be at least 3 ft. (1m) away from all 

electromagnetic interference (televisions, radios, etc.) sources. 

Interference is still possible even if this distance is maintained.

• Ensure any hanger used is strong enough to withstand the unit’s 

weight.

• If the indoor unit is installed in an unconditioned space, 

running for long periods of time when the temperatures are 
outside the recommended indoor unit operation ranges, it is 
recommended to seal all the corners of the indoor unit to 
prevent any leakage and add insulation material (13/32 to 13/
16 in (10-20 mm)) to the entire surface of the indoor unit to 
avoid condensation or heat transfer.

NOTE: Nuisance sweating may occur if the unit is installed in a 
high humidity environment with low airflow.

Table 3 — Operating Range

NOTE: DO NOT install the indoor or outdoor units in a location 
with special environmental conditions. For those applications, 
contact your Ductless representative

.

OPERATING RANGE

MIN/MAX °F (°C)

Cooling

Heating

Indoor DB

62 / 90 (17 / 32)

32 / 86 (0 / 30)

Indoor WB

59 / 84 (15 / 29)

PRODUCT INSTALLATION

• Installation must be performed by an authorized dealer or 

specialist. A defective installation can cause water leakage, 

electrical shock, or fire.

• The installation must be performed according to the installation 

instructions. Improper installation can cause water leakage, 

electrical shock, or fire. (In North America, installation must be 

performed in accordance with the requirements of NEC or CEC 

by authorized personnel only.)

• Contact an authorized service technician for repair or 

maintenance of this unit. This appliance must be installed in 

accordance with local codes.

• Only use the included accessories, parts, and specified parts for 

installation. Using non-standard parts can cause water leakage, 

electrical shock, fire, or unit failure. 

• Install drainage piping according to the instructions in this 

manual and in accordance with local codes. Improper drainage 

may cause water damage to your home and property.

• For units that have an auxiliary electric heater, 

DO NOT

 install 

the unit within 3 feet (1 meter) of any combustible materials.

DO NOT

 install the unit in a location that may be exposed to 

combustible gas leaks. If combustible gas accumulates around 

the unit, it may cause a fire.

DO NOT

 turn on the power until all work has been completed.

• When moving or relocating the system, consult experienced 

service technicians for the disconnection and re-installation of 

the unit.

WARNING

Securely install the indoor unit on a structure that can sustain its
weight. If the structure is too weak, the unit may fall and cause
personal injury, unit and property damage, or death.

DO NOT

 install the indoor unit in a bathroom or laundry room as

excessive moisture can short the unit and corrode the wiring.

WARNING

Install the indoor and outdoor units, cables and wires at least 3.2 ft 
(1m) from televisions, routers, computer equipment or radios to 
prevent static or image distortion. Depending on the appliances, a 
3.2 ft (1m) distance may not be sufficient. 

If the indoor unit is installed on metal, it must be electrically
grounded.

CAUTION

Содержание DLFLAA

Страница 1: ...work gloves Have a fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions included in the literature and attached to the unit Consult local building codes a...

Страница 2: ...allation parts and accessories to install the system Improper installation may result in water leakage electrical shock and fire or cause the equipment to fail Keep the installation manual in a safe p...

Страница 3: ...84 11 8 299 13 3 339 3 0 75 2 5 64 4 9 124 6 8 174 1 7 44 A HEIGHT 48 1 1222 C WIDTH 19 7 501 4 8 121 2 4 61 6 7 171 2 2 57 D DUCT 18 2 462 E DUCT 10 3 262 B DEPTH 21 1 535 0 8 21 0 5 13 0 6 16 18 4...

Страница 4: ...med according to the installation instructions Improper installation can cause water leakage electrical shock or fire In North America installation must be performed in accordance with the requirement...

Страница 5: ...t is installed over a finished ceiling and or living area building codes may require a field supplied secondary condensate pan to be installed under the entire unit Some localities may allow as an alt...

Страница 6: ...t 5 Install the drain lines Fig 7 Vertical Upflow Installations Fig 8 Horizontal Right Installations NOTE For a horizontal right installation secondary condensate pan field supplied must be installed...

Страница 7: ...d drain pan assembly 9 Reinstall the pipe temperature sensor in its original position Attach the room temperature sensor to the evaporator output pipe protection sleeve Fig 15 Reinstall the Pipe Tempe...

Страница 8: ...uipped with the electric auxiliary heat module please check the electric auxiliary heat module specification that is compatible with the unit to avoid unnecessary consequences caused by improper match...

Страница 9: ...into the opening made by removal of the sheet metal cover s Ensure the two support rod ends are on the opposite bulkhead Fig 24 Insert Heating Module 5 Use the 3 screws 6 screws for 15K or 20K remove...

Страница 10: ...quirements and local codes see Table 6 on page 11 Choose the power cord and the power cord installation location see Figure 30 Each circuit breaker group needs to connect to the power input line Where...

Страница 11: ...do not have a 90 degree elbow and 10ft 3m of main duct to first branch takeoff may require internal acoustical insulation lining As an alternative fibrous ductwork may be used if constructed and insta...

Страница 12: ...ood 2 Use a 2 5in 65mm core drill to drill a hole in the wall Make sure the hole is drilled at a slight downward angle so that the outdoor end of the hole is lower than the indoor end by about 0 5in 1...

Страница 13: ...g an airtight seal a After removing the burrs from the cut pipe seal the ends with PVC tape to prevent foreign materials from entering the pipe b Sheath the pipe with insulating material c Place flare...

Страница 14: ...nder to prevent kinking or damaging the tubing 6 After connecting the copper pipes to the outdoor unit wrap the power cable signal cable and the piping together with binding tape NOTE While bundling t...

Страница 15: ...ost positive way of assuring a system is free of air and moisture see Fig 49 NOTE DO NOT add a filter line drier Fig 49 Deep Vacuum Graph Triple Evacuation Method The triple evacuation method should b...

Страница 16: ...it would lose power A disconnect switch is not required on the indoor unit side on the wiring between the outdoor and indoor unit A 3 pole disconnect purchased separately may be used for extra protect...

Страница 17: ...e is a ground wire To minimize voltage drop the factory recommended wire size is 14 2 power stranded with a ground Communication Wiring A separate 2 wire cable stranded shielded copper conductor with...

Страница 18: ...0 5 0 20 120 36 5 0 42 250 48 5 0 65 400 3 S 1 L1 2 L2 208 230 1 60 Power Supply Main 1 L1 208 230 1 60 2 L2 3 S 1 L1 2 L2 CONNECTING CABLE OUTDOOR TO INDOOR Indoor Unit Power Supply 208 230 1 60 Indo...

Страница 19: ...Indoor Unit Control Box Sizes 36 48 LED Display The control displays active faults codes on the LED display When the control displays the fault code and the LED flashes quickly there is something wro...

Страница 20: ...nnected b Turn off the power to the indoor and outdoor units for 3 minutes c Turn the power back on Wait 1 minute and check the 24 volt Interface digital display If the display reads 00 then proceed I...

Страница 21: ...troller exits the MODIFICATION mode After you power OFF the unit power the unit ON again and the unit retains the setting value Fig 65 RG57 Remote Controller FP Activate Disable freeze protection func...

Страница 22: ...1 400 1 310 1 215 1 105 950 825 Low 1 525 1 450 1 372 1 280 1 190 1 074 935 785 650 36 SP1 High 1 335 1 270 1 165 1 062 950 810 645 450 240 Medium 1 185 1 100 990 845 685 520 335 Low 1 020 915 775 60...

Страница 23: ...Pressurein WC High Medium Low SP4 0 200 400 600 800 1 000 1 200 1 400 1 600 1 800 2 000 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Air ow CFM Sta cPressurein WC High Medium Low SP1 0 200 400 600 800 1 000 1...

Страница 24: ...M Sta cPressurein WC High Medium Low SP2 0 200 400 600 800 1 000 1 200 1 400 1 600 1 800 2 000 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Air ow CFM Sta c Pressurein WC High Medium Low SP3 0 200 400 600 800...

Страница 25: ...conditioner Turn off the main power switch and reinstall the test cover NOTE If the unit malfunctions or does not operate according to your expectations please refer to the Troubleshooting section of...

Страница 26: ...FF E0 Indoor unit EEPROM parameter error 2 times OFF E1 Indoor outdoor unit communication error 4 times OFF E3 The indoor fan speed is operating outside of the normal range 5 times OFF E4 Indoor room...

Отзывы: