V. Refrigerating circuit
Installation & Maintenacne Manual
No refrigerant replenishment is required if extended length of fitting pipe is less than 7m.
If extended length of fitting pipe is over 7m, replenishing volume of refrigerant should be
calculated as per the following formula: replenishing volume Xg=15g/mX(A-7)m
Outdoor unit
Indoor
unit
Maximum height difference 5m
(regardless either unit is higher)
Max. Lenth of extended fitting pipe
Refrigerant replenishment (R22:g):
Refrigerating circuit for heat pump type
Capillary(heating)
Room-temperature
thermistor RT11
Pipe-temperature
thermisto
Indoor unit
Outdoor unit
Indoor
heat
exchanger
Outdoor
heat
exchanger
Flow direction of refrigerant
for cooling
Flow direction of refrigerant
for heating
Joint of flared pipe
Connecting pipe
(with heat-insulating
pipe casing)
Joint of flared pipe
Connecting pipe
(with heat-insulating
pipe casing)
Shutoff valve
(with access door)
Shutoff valve
4-way valve
Compressor
Check valve
Capillary(cooling)
Содержание CSU 12HCAA
Страница 42: ...5K 7K 9K series outdoor unit 40 Installation Maintenance Manual 2 3 4 5 6 7 8 9 19 VIII Parts list...
Страница 48: ...2005 12 20...
Страница 49: ......
Страница 57: ...9 59...
Страница 59: ...11 59...
Страница 60: ...12 59...
Страница 61: ...13 59...
Страница 62: ...14 59...
Страница 63: ...15 59...
Страница 64: ...16 59...
Страница 65: ...17 59...
Страница 66: ...18 59...
Страница 67: ...19 59 Installation Guide 4 Indoor unit and outdoor unit explosion diagram and spare parts list...
Страница 68: ...20 59 CS 23H3 V77AY1A CS 25H3 V AY1A CS 32H3 V AH4 INDOOR UNIT...
Страница 69: ...21 59 CS 51H3 H AH1 INDOOR UNIT...
Страница 70: ...22 59 CS 66H3 N AS INDOOR UNIT...
Страница 71: ...23 59 CS 88H3 Q AT INDOOR UNIT...
Страница 72: ...24 59 KFR 23GW AC CS 25H3 V AY1A OUTDOOR UNIT...
Страница 73: ...25 59 CS 32H3 V AH4 OUTDOOR UNIT...
Страница 74: ...26 59 CS 51H3 H AH1 OUTDOOR UNIT...
Страница 75: ...27 59 CS 66H3 N AS OUTDOOR UNIT...
Страница 76: ...28 59 CS 88H3 Q AT OUTDOOR UNIT...