Turn off power
supply once, and
turn it on again.
Does
compressor
continue to
operate?
Start to operate indoor
unit in cooling
operation at airflow
level
“
LOW
”
,wait
three minutes..
Does indoor
fan operate?
Fan motor
operates
normally.
Is it possible to detect AC
220V between
pin(high/middle/low) and
pin(common) of motor
connector .
Replace indoor
fan motor.
Replace main
P.C. board.
Replace
bearing.
YES
YES
YES
NO
NO
NO
Turn off indoor unit and rotate
cross-flow fan by hand when the
unit is on standby.Is it possible to
rotate cross-flow fan by hand
properly?
Only indoor fan motor does not operate.
Is capacitor of indoor fan ok?
YES
NO
YES
Replace
capacitor
NO
<Primary check>
(1) Is it possible to detect the power supply voltage (200-240V) between L and N on the terminal
block?
(2) Does the indoor fan motor operate in cooling operation?
Содержание CSU 12HCAA
Страница 42: ...5K 7K 9K series outdoor unit 40 Installation Maintenance Manual 2 3 4 5 6 7 8 9 19 VIII Parts list...
Страница 48: ...2005 12 20...
Страница 49: ......
Страница 57: ...9 59...
Страница 59: ...11 59...
Страница 60: ...12 59...
Страница 61: ...13 59...
Страница 62: ...14 59...
Страница 63: ...15 59...
Страница 64: ...16 59...
Страница 65: ...17 59...
Страница 66: ...18 59...
Страница 67: ...19 59 Installation Guide 4 Indoor unit and outdoor unit explosion diagram and spare parts list...
Страница 68: ...20 59 CS 23H3 V77AY1A CS 25H3 V AY1A CS 32H3 V AH4 INDOOR UNIT...
Страница 69: ...21 59 CS 51H3 H AH1 INDOOR UNIT...
Страница 70: ...22 59 CS 66H3 N AS INDOOR UNIT...
Страница 71: ...23 59 CS 88H3 Q AT INDOOR UNIT...
Страница 72: ...24 59 KFR 23GW AC CS 25H3 V AY1A OUTDOOR UNIT...
Страница 73: ...25 59 CS 32H3 V AH4 OUTDOOR UNIT...
Страница 74: ...26 59 CS 51H3 H AH1 OUTDOOR UNIT...
Страница 75: ...27 59 CS 66H3 N AS OUTDOOR UNIT...
Страница 76: ...28 59 CS 88H3 Q AT OUTDOOR UNIT...