Table 2-1.2: Specifications
kW
30
60
Model name
MC-SU30M-RN1L
MC-SU60M-RN1L
Power supply
V/Ph/Hz
380-415/3/50
Cooling
1
Capacity
kW
28.2
55
Rated input
kW
10.93
22.54
EER
2.58
2.44
SEER
3.72
3.73
Heating
2
Capacity
kW
30.8
60
Rated input
kW
10.62
21.2
COP
2.90
2.83
SCOP
3.27
3.45
Seasonal space heating energy efficiency class
A+
A+
Max. running current
A
19.7
36.9
Air side heat
exchanger
Type
Finned tube
Finned tube
Fan motor type
DC motor
DC motor
Fan motor quantity
1
2
Air flow rate
12,500
24,000
Water side heat
exchanger
Type
Plate
Plate
Volume
L
2.44
5.17
Water flow
m
3
/h
5
9.8
Pump head
m
18
15
Water pressure drop
kPa
55
61
Refrigerant system
Refrigerant type
R410A
R410A
Refrigerant charge
kg
10.5
17.0
Throttle type
EXV
EXV + Capillary
Sound power level
dB(A)
78
87
Sound pressure level
3
dB(A)
68
73
Net dimensions (W×H×D)
mm
1870×1175×1000
2220×1325×1055
Packed dimensions (W×H×D)
mm
1910×1225×1035
2250×1370×1090
Net/Gross weight
kg
335/345
515/525
Pipe connections
Water inlet/outlet
mm
DN40
DN50
Controller
Wired controller
Wired controller
Operating temperature
range
Cooling
°C
-10 to 43
-10 to 43
Heating
°C
-15 to 30
-15 to 30
Water outlet
temperature range
Cooling
4
°C
5 to 20
5 to 20
Heating
°C
25 to 55
25 to 55
Notes:
1.
Cooling: Chilled water inlet/outlet temp.12/7°C; outdoor ambient temp. 35°C DB.
2.
Heating: Warm water inlet/outlet temp. 40/45°C; outdoor ambient temp. 7°C DB/6°C WB.
3.
Sound pressure level is measured at a position 1m in front of the unit and 1.1m above the floor in a semi-anechoic chamber.
4.
Capacity and efficiency data calculated in accordance with EN14511.