Trouble Chart

    6. Open the charging door, make sure any door open interlock is   
      temporarily by-passed and repeat trial for ignition.

      a. Open main manual shut-off  valve. With main fl ame present,    
        close charging door, remove temporary door open interlock    
        and check incineration chamber pressure. Burner peep hole
        can be used for access to obtain approximate reading 
        (See Figure 3). Make sure sensing tube extends into the      
        incineration chamber at least 6″. Pressure should be 
        between 0″ to minus 0.5″ W.C. for J81A, 0″ to minus 1.0″ 
        W.C. for J121A. If pressure is on the high negative side of
         the range, increase the ignitor fl ame gas pressure to 4.0″ to    
        5.0″ W.C. 

      b. No fl ame present, clean and reset electrode assembly per     
        Figure 5 and repeat Step 6a. 

  A. With motor running, confi rm 120 volts as follows:
    1. Between strip terminals L1 and L2: 120 volts present, voltage    
      OK.
    2. Between strip terminals L1 and ground: 120 volts present,       
      ground OK.
    3. Between strip terminals L2 and ground: No voltage, neutral      
      OK.
  B. Follow test procedure as specifi ed in Step 2A. 
    1. Disconnect fl ame electrode wire and check for continuity.
    2. Connect DC voltmeter in test jack in amplifi er. With ignitor       
      fl ame on, reading should be at 2 or more volts DC and steady.
      Adjust ignitor gas pressure to obtain acceptable signal and
      note gas pressure and signal strength for future reference.
  C. If all checks listed above were satisfactory and the ignitor will not  
     stay lit, fl ame safeguard defective.

  A. Confi rm 120 volts between strip terminal L2 and 8.
    1. 120 volts present, continue with Step B.
    2. No voltage, fl ame safeguard defective.
  B. Connect manometer to main automatic valve downstream        
     pressure tap.
    1. No gas pressure when valve is energized.
      a. Confi rm that pressure of at least 5.5″ W.C. NATURAL,
        8.0″ W.C. PROPANE, is available at the inlet of the main      
        automatic valve.
      b. Pressure at inlet side OK, main automatic valve defective.

  A. Low gas pressure.
  B. Air shutter open too far.
  C. Input adjuster not set properly.

  A. High gas pressure.
  B. Air shutter closed too far.
  C. Insuffi  cient free air in incineration chamber.
  D. Dirty blower wheel.
  E. Input adjustor open too far for air shutter setting.

  A. Main automatic and/or ignitor gas valve defective.
  B. High gas pressure.

3  Ignitor Flame on Only 
During the 4 or 10 
Second Trial for Ignition

4  Ignitor Lights But No 
Main 

fl

 ame

5  Short Main Flame

6  Long Hazy Main Flame

7  Gas Fails to Shut O

 

Trouble Chart

Continued

2  Motor Runs 
Continuously But No Flame 
and Burner Housing Cool
Continued

Содержание Incinomite J121A-3

Страница 1: ...any phone in your building Immediately phone your gas supplier from another building Follow the gas supplier s instructions If you cannot reach your gas supplier call the re department Installation an...

Страница 2: ...zontal or 10 down ring NOTE Burner components are UL recognized CGA listed CSA certi ed and or AGA design certi ed mounted and wired The complete burner is re tested 1 Standard burners are shipped as...

Страница 3: ...ude into the incineration chamber If necessary build an extension outside of the incinerator wall to increase wall depth To change the Mounting Flange to its alternate position horizontal or 10 down r...

Страница 4: ...essive gas pressure is prevalent the regulator must be a tight shut o type to prevent high pressures from developing during stand by The regulator must have a minimum ow regulating capacity for the ig...

Страница 5: ...r to SPECIFICATIONS page 2 for ampacity Con rm that the polarity is correct hot wire to strip terminal L1 neutral L2 and that the neutral line is not subject to induced low voltage check L2 to ground...

Страница 6: ...r Ignitor Ignition Flame Safeguard and motor are powered There will be a delay until blower reaches operating speed and trips blower proving switch When the blower proving switch is made the Ignitor S...

Страница 7: ...Adjuster Setting in Numbers of Turns from Full Closed Propane Gas 2 500 BTU Cu Ft with 3 8 Main Gas Port Natural Gas 1 000 BTU Cu Ft with 5 8 Main Gas Port Gas Pressure at Main automatic Valve Inches...

Страница 8: ...h the charging door open and then with it closed Remove any temporary Door Open bypasses installed in Step 6 14 Test operation of any auxiliary operating and or limit controls 15 Load incinerator and...

Страница 9: ...ration of the ame sensor rod can be checked by measuring the ame signal With the Flame Safeguard energized and only the ignitor burning a good reading should run steady 2 or more volts DC When servici...

Страница 10: ...ose air adjustment screw Adjust the screw up or down to nd the best Flame Signal or until repeatable and stable lighto s are achieved Ignitor air ow is decreased as the screw is turned clockwise and i...

Страница 11: ...low pressure setting should be raised until the burner shuts o Reduce the setting and set the low pressure switch to restart the burner Reduce the high pressure setting until the burner shuts o Then r...

Страница 12: ...witch or timer open and or remote switch or timer open 4 L2 and 4 No voltage optional high or low gas pressure switch is tripped 5 L2 and Thermal switch terminal 1 black wire a No voltage thermal swit...

Страница 13: ...est jack in ampli er With ignitor ame on reading should be at 2 or more volts DC and steady Adjust ignitor gas pressure to obtain acceptable signal and note gas pressure and signal strength for future...

Страница 14: ...st Victoria Street Chicago Illinois 60646 toll free 866 705 0514 tel 773 604 8700 fax 866 580 8700 web www midcointernational com e mail sales midcointernational com 14 Printed in USA ISO 9001 C O MPA...

Отзывы: