Midco Incinomite J121A-3 Скачать руководство пользователя страница 12

12

Midco 

International

 Inc.

8470 70

Service & Trouble Chart

The Thermal Switch is a heat sensitive single pole double throw snap switch that energizes the 
blower motor to provide cooling air if, because of a heat back up through the burner when the motor 
is off , the temperature of the blower housing reaches 160° F. The thermal switch is not wired into the 
gas valve circuit and does not turn valve off  when activated by heat back up.

The switch mechanism is a bi-metallic disc that snaps over when it is heated to the set temperature. 
The switch is mounted so that the disc bears against the side plate of the blower housing.

Testing the switch to prove that it is functional can be done by removing the ignitor assembly and 
blowing hot air through the opening toward the blower inlet. If hot air is not available, remove the 
switch and check for continuity. With the switch cool, there should be continuity between terminals 1 
(black wire) and 3 (red/white). To simulate the “hot” condition, place the switch on a fi rm surface and 
apply fi nger pressure to the switch disc. When the disc “snaps”, there should be continuity between 
terminals 1 and 2 (yellow/black wire).
 

  

 

 

_______________________________________

Make sure the switch or timer is calling for heat. Defective wiring or loose connections can simulate 
outlined below. Check associated wiring before replacing a component.
 

ELECTRICAL AND FLAME CHECKS MUST BE MADE IN THE ORDER LISTED. 

  A . Confi rm 120 volts between strip terminals.
    1. L2 and L1: No voltage, fused disconnect off  or fuse open.
    2. L2 and 3: No voltage, safety controls open.
    3. L2 and 10: No voltage, burner switch or timer open and/or remote switch or timer open.
    4. L2 and 4: No voltage, optional high or low gas pressure switch is tripped.
    5. L2 and Thermal switch terminal 1 (black wire):
      a. No voltage, thermal switch is defective.
      b. Voltage present, defective Motor.

  A. Make certain Flame Safeguard lockout switch is not tripped.

    CAUTION: Tests are valid only during the 4 or 10 second trial for ignition. Main Manual 
Shut-Off  Valve must be closed and Manual Ignitor Valve open.

    1. Confi rm 120 volts on strip terminals L2 and 5.
      a. Voltage present: Continue to Step 2.
      b. No voltage:
        J81A - Motor interlock switch defective.
        J121A - Blower air switch defective.
    2. Confi rm 120 volts between strip terminal L2 and terminal 6.
      a. Voltage present, continue to Step 3.
      b. No voltage, fl ame safeguard defective.
    3. Confi rm 120 volts on strip terminal L2 and 7.
      a. Voltage present, continue to Step 4.
      b. No voltage, fl ame safeguard defective.
    4. Check for ignition spark (spark length approximately 1/8″).
      a. Between spark generator hi-voltage terminal and ground: No spark, defective spark    

 

         generator.
      b. Between spark electrode wire and chassis ground: No spark, spark generator defective.
      c. For checking spark gap between spark electrode and ground barrier, refer to Part 2    

 

        Service VIII Ignitor and Regulator Assembly, Spark Test.
    5. Connect manometer to ignitor gas pressure test tap, and check pressure during trial for   

 

       ignition period.
      a. No pressure, confi rm that pressure of at least 5.5″ W.C. is available at the inlet of the   

 

        ignitor gas valve, and repeat Step 5. If still no ignitor gas pressure, ignitor gas valve    

 

        defective.
      b. Ignitor gas pressure 3.0″ to 4.0″ W.C., continue with Step 6.
      c. Adjust the ignitor regulator to 3.5″ W.C. while gas is fl owing.

  XIV  Thermal Switch

Trouble Chart

1  Motor Will Not Run

2  Motor Runs 
Continuously But No Flame 
and Burner Housing Cool

!

Содержание Incinomite J121A-3

Страница 1: ...any phone in your building Immediately phone your gas supplier from another building Follow the gas supplier s instructions If you cannot reach your gas supplier call the re department Installation an...

Страница 2: ...zontal or 10 down ring NOTE Burner components are UL recognized CGA listed CSA certi ed and or AGA design certi ed mounted and wired The complete burner is re tested 1 Standard burners are shipped as...

Страница 3: ...ude into the incineration chamber If necessary build an extension outside of the incinerator wall to increase wall depth To change the Mounting Flange to its alternate position horizontal or 10 down r...

Страница 4: ...essive gas pressure is prevalent the regulator must be a tight shut o type to prevent high pressures from developing during stand by The regulator must have a minimum ow regulating capacity for the ig...

Страница 5: ...r to SPECIFICATIONS page 2 for ampacity Con rm that the polarity is correct hot wire to strip terminal L1 neutral L2 and that the neutral line is not subject to induced low voltage check L2 to ground...

Страница 6: ...r Ignitor Ignition Flame Safeguard and motor are powered There will be a delay until blower reaches operating speed and trips blower proving switch When the blower proving switch is made the Ignitor S...

Страница 7: ...Adjuster Setting in Numbers of Turns from Full Closed Propane Gas 2 500 BTU Cu Ft with 3 8 Main Gas Port Natural Gas 1 000 BTU Cu Ft with 5 8 Main Gas Port Gas Pressure at Main automatic Valve Inches...

Страница 8: ...h the charging door open and then with it closed Remove any temporary Door Open bypasses installed in Step 6 14 Test operation of any auxiliary operating and or limit controls 15 Load incinerator and...

Страница 9: ...ration of the ame sensor rod can be checked by measuring the ame signal With the Flame Safeguard energized and only the ignitor burning a good reading should run steady 2 or more volts DC When servici...

Страница 10: ...ose air adjustment screw Adjust the screw up or down to nd the best Flame Signal or until repeatable and stable lighto s are achieved Ignitor air ow is decreased as the screw is turned clockwise and i...

Страница 11: ...low pressure setting should be raised until the burner shuts o Reduce the setting and set the low pressure switch to restart the burner Reduce the high pressure setting until the burner shuts o Then r...

Страница 12: ...witch or timer open and or remote switch or timer open 4 L2 and 4 No voltage optional high or low gas pressure switch is tripped 5 L2 and Thermal switch terminal 1 black wire a No voltage thermal swit...

Страница 13: ...est jack in ampli er With ignitor ame on reading should be at 2 or more volts DC and steady Adjust ignitor gas pressure to obtain acceptable signal and note gas pressure and signal strength for future...

Страница 14: ...st Victoria Street Chicago Illinois 60646 toll free 866 705 0514 tel 773 604 8700 fax 866 580 8700 web www midcointernational com e mail sales midcointernational com 14 Printed in USA ISO 9001 C O MPA...

Отзывы: