Midco Incinomite J121A-3 Скачать руководство пользователя страница 10

10

Midco 

International

 Inc.

8470 70

Service

SPARK TEST

—Main Manual Shut-Off  Valve must be off . Place the Ignitor Assembly on top of the 

burner with the electrode ends visible and good metal to metal contact between the Ignitor Mounting 
Plate and the burner chassis. 

Connect the high voltage wire to the spark electrode. Spark should be visible during trial for ignition 
period and arc from the electrode end to the Ground Barrier. It should be audible and visible, though 
it is rather thin and diffi  cult to see in bright light. 

If the spark is not audible or visible it is leaking directly to ground. Before removing electrodes, 
check to make sure voltage is available by positioning the spark wire 1/8″ from the end of the 
electrode. If necessary, press relay reset button to recycle ignition sequence. 

Disconnect Flame Electrode

 wire and switch the high voltage wire to the fl ame electrode and 

repeat test for insulator leakage.

    CAUTION: Do not indiscriminately change the ignitor gas orifi ce size as ignition troubles 
are rarely cured in this manner. The ignitor utilizes a premixed gas/air mixture and, as the 
air input is relatively fi xed, any adjustment to the gas/air ratio that might be required for a 
specifi c application should be made by careful adjustment of the ignitor regulator to vary 
its outlet gas pressure. Pressure adjustments must be made when the gas is fl owing. If 
cleaning and electrode adjustment does not eliminate an ignition problem, further checks are 
required. Refer to Trouble Chart.

 

  

 

 

_______________________________________

The ignitor assembly as shipped is pre-set during factory fi re-testing and normally needs no 
adjustment except in installations where the air shutter is full open. The ignitor should not 
be adjusted until it is confi rmed that good lightoff s are not possible with ignitor gas pressure 
adjustments only as described in Section VIII.

The Air adjustment screw is located under a plug button in the Ignitor Block about 1⁄2 inch behind 
the Ignitor Orifi ce (refer to Figure 4). A 5⁄64 (.078) inch hexagon wrench is required for adjustment. 
Pry up the plug button to expose air adjustment screw. Adjust the screw up or down to fi nd the best 
Flame Signal or until repeatable and stable lightoff s are achieved. Ignitor airfl ow is decreased as the 
screw is turned clockwise, and increased as it is turned counterclockwise. Generally 3 to 5 turns up 
from full closed (screw bottomed out) works best.

When adjustments are completed, replace plug button to protect adjustment screw
 

  

 

 

_______________________________________

    WARNING: Explosion hazard. Do not use this device if it gets wet. It can malfunction and 
cause serious injury or death. Replace any device that has been wet.

Standard Incinomite J Series burners are equipped with a Honeywell RM7890 microprocessor 
based burner control employing a fl ame rectifi cation system of fl ame detection. Burner construction 
for special codes and/or insurance requirements such as Factory Mutual or Industrial Risk Insurers 
(IRI) may require alternate controls. (Refer to Section XI SPECIAL EQUIPMENT). A safe start and 
run control sequence is provided with instantaneous response to presence or loss of fl ame signal. 
Flame failure response time is .8 seconds. Pilot Flame Establishing Period (PFEP) is fi eld selectable 
from 4 or 10 seconds. The RM7890 features a plug in amplifi er. Five LED’s (light emitting diodes) 
are provided to display sequence information. Refer to the Honeywell RM7890 literature for detailed 
operating information, confi guration requirements, testing, and service.

Initiate (“Power” LED is lit)

The RM7890 enters the INITIATE sequence when it is powered. The INITIATE sequence lasts for 
ten seconds unless the voltage or frequency tolerances are not met (refer to Honeywell RM7890 
literature for criteria). When tolerances are met, the INITIATE sequence will restart. If the condition 
is not corrected and the hold condition exists for four minutes, the RM7890 will lock-out. Causes for 
hold conditions in the INITIATE sequence are in the Honeywell RM7890 literature. 

Standby (“Power” LED is lit)

The RM7890 is idle in this state of sequencing. When the burner switch, limits, operating limit 
controls, and all microprocessor monitored circuits are in the correct state for RM7890 to continue, 
sequencing will advance to 

IGNITION TRIAL

VIII  Ignitor and 
Regulator Assembly
Continued

!

IX  Ignitor Gas / Air 
Adjustment (J121A-3 Only) 

X  Flame Safeguard

!

Содержание Incinomite J121A-3

Страница 1: ...any phone in your building Immediately phone your gas supplier from another building Follow the gas supplier s instructions If you cannot reach your gas supplier call the re department Installation an...

Страница 2: ...zontal or 10 down ring NOTE Burner components are UL recognized CGA listed CSA certi ed and or AGA design certi ed mounted and wired The complete burner is re tested 1 Standard burners are shipped as...

Страница 3: ...ude into the incineration chamber If necessary build an extension outside of the incinerator wall to increase wall depth To change the Mounting Flange to its alternate position horizontal or 10 down r...

Страница 4: ...essive gas pressure is prevalent the regulator must be a tight shut o type to prevent high pressures from developing during stand by The regulator must have a minimum ow regulating capacity for the ig...

Страница 5: ...r to SPECIFICATIONS page 2 for ampacity Con rm that the polarity is correct hot wire to strip terminal L1 neutral L2 and that the neutral line is not subject to induced low voltage check L2 to ground...

Страница 6: ...r Ignitor Ignition Flame Safeguard and motor are powered There will be a delay until blower reaches operating speed and trips blower proving switch When the blower proving switch is made the Ignitor S...

Страница 7: ...Adjuster Setting in Numbers of Turns from Full Closed Propane Gas 2 500 BTU Cu Ft with 3 8 Main Gas Port Natural Gas 1 000 BTU Cu Ft with 5 8 Main Gas Port Gas Pressure at Main automatic Valve Inches...

Страница 8: ...h the charging door open and then with it closed Remove any temporary Door Open bypasses installed in Step 6 14 Test operation of any auxiliary operating and or limit controls 15 Load incinerator and...

Страница 9: ...ration of the ame sensor rod can be checked by measuring the ame signal With the Flame Safeguard energized and only the ignitor burning a good reading should run steady 2 or more volts DC When servici...

Страница 10: ...ose air adjustment screw Adjust the screw up or down to nd the best Flame Signal or until repeatable and stable lighto s are achieved Ignitor air ow is decreased as the screw is turned clockwise and i...

Страница 11: ...low pressure setting should be raised until the burner shuts o Reduce the setting and set the low pressure switch to restart the burner Reduce the high pressure setting until the burner shuts o Then r...

Страница 12: ...witch or timer open and or remote switch or timer open 4 L2 and 4 No voltage optional high or low gas pressure switch is tripped 5 L2 and Thermal switch terminal 1 black wire a No voltage thermal swit...

Страница 13: ...est jack in ampli er With ignitor ame on reading should be at 2 or more volts DC and steady Adjust ignitor gas pressure to obtain acceptable signal and note gas pressure and signal strength for future...

Страница 14: ...st Victoria Street Chicago Illinois 60646 toll free 866 705 0514 tel 773 604 8700 fax 866 580 8700 web www midcointernational com e mail sales midcointernational com 14 Printed in USA ISO 9001 C O MPA...

Отзывы: