background image

Part 1 Installation

Specifications 

The  

ECONOMITE  Model RE 4400DS HTD (High Turn Down) 

burners with direct spark

ignition are adaptable to most gas utilization equipment. 

AIR DELIVERY (Approximate Air Delivery at Zero Draft)

RE4400DS HTD ..... 87 SCFM

1

FIRING RATE (NATURAL )

(Based on 0 draft over fire pressure)

MAXIMUM  MBH

3

400

MINIMUM  MBH

3

20

GAS SUPPLY PRESSURE REQUIRED

Min

Max

250 MBH ................................................... 7.0" to 14.0" W.C

350 MBH ................................................... 7.0" to 14.0" W.C

400 MBH ................................................... 7.0" to 14.0" W.C

TUBE DIAMETER ........................................................... 4"

RECOMMENDED COMBUSTION CHAMBER SIZE (AT MAX. BTU/HR)

WIDTH

10"

LENGTH

16.5"

ELECTRICAL SUPPLY 

.....................................120 VAC...........60 Hertz

ELECTRONIC CONTROL VOLTAGE ................ 24 VAC

FLAME SAFETY....Direct Spark Ignition of Main Flame, Electronic Safety

TABLE 1: 

Burner Specifications

1.

SCFM = Standard Cubic Feet / Minute.

2.

All Ratings Based on 1000 BTU/Cu. Ft. NATURAL Derate burner for altitude over 2,000 feet by 
4% for each 1,000 feet above sea level.

3.

1 MBH = 1,000 BTU/hr.

4.

Burners available in 115V, 208V or 230V power supply. Consult burner name plate for correct
power supply, or as recommended by the equipment manufacturer.

____________________________

The burner tube, or the stainless steel sleeve that is included with the burner, must be

sealed air tight into the combustion chamber opening with refractory material.  The sleeve is
preferred as it is designed to properly locate the end of the tube relative to the inside wall of
the combustion chamber, and to permit burner removal 

or as recommended by the equipment

manufacturer

.

CAUTION: In no case should the burner tube be  allowed to extend into the

chamber because high combustion chamber temperatures will cause premature
electrode, burner tube and sleeve deterioration.

____________________________

CAUTION:Refer to wiring diagram in Figure 1 or located on the burner

housing.

Installation wiring and grounding to the burner must conform to local codes, or, in their
absence in the 

United States

to 

National Electric Code, ANSI/NFPA No. 70

latest edition;

in 

Canada, to Canadian Electrical Code Part 1, CSA Standard C22.1

Use copper wire not less than 14 gage for line voltage wiring. Hook up to a dedicated line

with an on-off disconnect switch and a minimum 10 Amp breaker, or as required by
equipment manufacturer.

The frame of the burner should be well grounded. A ground lug is located in control box

for positive grounding where insulated pipe couplings are used or where any doubt exists
regarding grounding sufficiency.

Confirm that the polarity is correct—hot wire to strip terminal L1, neutral L2—and that the

neutral line is not subject to induced low voltage (check L2 to earth ground) from other
equipment, as that can cause the Electronic Control to malfunction.

Each installation must include suitable limit control(s). 

CAUTION:  Label all wires prior to disconnection when servicing controls.

Wiring errors can cause improper and dangerous operation. Verify proper operation
after servicing.

Part 1 

Installation

2

I

Combustion

Chamber

II

Electrical

Содержание Economite RE4400DS

Страница 1: ...ry to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately phone your gas supplier from another building Follow the gas supplier s instructions If y...

Страница 2: ...ion chamber and to permit burner removal or as recommended by the equipment manufacturer CAUTION In no case should the burner tube be allowed to extend into the chamber because high combustion chamber...

Страница 3: ...ximum firing rate of the burner the gas supply piping must be sized to provide a minimum pressure of 7 0 W C Natural for 400 MBH to the inlet of the combination redundant valve when the burner and all...

Страница 4: ...rop however the size must be sufficient to deliver burner rating pressure CAUTION High gas pressure supply lines require the proper pressure reducing regulators Install a high pressure regulator of th...

Страница 5: ...Do not purge into the gas utilization equipment 3 To purge the gas utilization equipment and chimney of any accumulated gases turn main Manual Gas Cock OFF turn burner power on and set operating cont...

Страница 6: ...r by checking the flue gases with an ORSAT or similar combustion testing instrument The carbon monoxide content should conform to local codes or in their absence to the level specified in the United S...

Страница 7: ...o provide the correct gas flow for the burner Refer to Table 3 for the correct maximum fire manifold pressure settings If the burner lights and then loses the DC micro Amp flame signal it will retry t...

Страница 8: ...r reduce the air vary the alignment between the damper and the inlet ring Minimum air shutter adjustment can be done by adjusting the three 8 18 screws on the inlet ring see Figure 5 To increase or de...

Отзывы: