background image

After checking for leaks, purge the gas line up to the burner inlet. Purging the air from the

gas supply line at this step will expedite the first light-off.

NOTE: 

If there is more than 1.0" W.C. differential in the inlet pressure to the burner

compared to when all other gas utilization equipment are off, refer to Section VII.

____________________________

Burners are approved for use with NATURAL gas and should be used only with the gas
specified on the rating plate. 

The gas input should be set at the heating rate determined by the building heat loss and/or

heating plant survey, but not exceeding the rated maximum input of the gas utilization
equipment or Economite burner.

____________________________

WARNING: Ignition is automatic. Make spark observations into combustion

chamber only with Main Manual Shut-Off Valves closed. Confirm that gas utilization
equipment does not contain any accumulated gases. Purge as described in step 3
below.

CAUTION: Cover plates, guards, and enclosures must be maintained in place

at all times except during maintenance and service.  

1.

Check the burner piping and valves for gas leaks by applying a  weak  liquid soap 
solution to unions and joints with the gas supply on. Leakage will be indicated by the 
appearance of soap bubbles. Locate and correct all gas leaks before proceeding.

WARNING: DO NOT USE OPEN FLAME.

2.

Purging the air from the gas supply line at this  step will expedite first light-off.

IMPORTANT: 

Purge outside the building. Do not purge into the gas utilization 

equipment.

3.

To purge the gas utilization equipment and chimney of any accumulated  gases, turn 
main Manual Gas  Cock 

OFF

,  turn burner power on, and set operating control to 

ON

or

thermostat to call for heat. Let the blower run long enough to accomplish four 
combustion chamber volume air changes, but not less  than five minutes.

CAUTION:Make sure that the capacity range of the burner, manifold pressure,

and the preliminary combustion air shutter setting are suitable for capacity rating of
the gas utilization equipment.  Refer to Section V and Table 3. 

WARNING:  Repeated unsuccessful attempts to light will result in

accumulated gases in gas utilization equipment and  chimney.  To  prevent  these
gases  from  reaching  an explosive level, periodically purge the gas utilization
equipment and or chimney as described in step 3 above.

4.

To make a preliminary setting of the burner input, determine the manifold gas pressure
required from Table 3 and adjust the Main Gas Pressure Regulator on the combination
gas valve accordingly. 

5

Part 1 

Installation Continued

Part 1 Installation

IV

Main Gas

Input Selection

V

Initial Start-

up /Adjustment 

Table 3:  

Capacity and Preliminary Gas Settings

1

. Adjust the main regulator to vary the manifold gas pressure and burner input within the range

shown.  Do not exceed  pressure as listed in Table 3, under any circumstances. Use combustion
readings (CO and O2) and a flow meter to determine exact inputs.

DATA FOR TABLE  IS APPROXIMATE AND BASED

ON “0" OVERFIRE PRESSURE AT SEA LEVEL 

Natural Gas Pressure Settings 

4.5

3.5

1.8

400

350

250

Input
MBH

Natural Gas

Manifold 

1

Pressure
("W.C)

RE4400DS HTD (High Fire Settings)

Содержание Economite RE4400DS

Страница 1: ...ry to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately phone your gas supplier from another building Follow the gas supplier s instructions If y...

Страница 2: ...ion chamber and to permit burner removal or as recommended by the equipment manufacturer CAUTION In no case should the burner tube be allowed to extend into the chamber because high combustion chamber...

Страница 3: ...ximum firing rate of the burner the gas supply piping must be sized to provide a minimum pressure of 7 0 W C Natural for 400 MBH to the inlet of the combination redundant valve when the burner and all...

Страница 4: ...rop however the size must be sufficient to deliver burner rating pressure CAUTION High gas pressure supply lines require the proper pressure reducing regulators Install a high pressure regulator of th...

Страница 5: ...Do not purge into the gas utilization equipment 3 To purge the gas utilization equipment and chimney of any accumulated gases turn main Manual Gas Cock OFF turn burner power on and set operating cont...

Страница 6: ...r by checking the flue gases with an ORSAT or similar combustion testing instrument The carbon monoxide content should conform to local codes or in their absence to the level specified in the United S...

Страница 7: ...o provide the correct gas flow for the burner Refer to Table 3 for the correct maximum fire manifold pressure settings If the burner lights and then loses the DC micro Amp flame signal it will retry t...

Страница 8: ...r reduce the air vary the alignment between the damper and the inlet ring Minimum air shutter adjustment can be done by adjusting the three 8 18 screws on the inlet ring see Figure 5 To increase or de...

Отзывы: