background image

DANGER:  Explosion hazard.

Do not use oxygen for pressure testing.

An explosion could occur during initial start up.

 

If the burner piping must be rearranged because of space limitation, be sure to carry out

the general arrangement shown in Figure 2. Install the combination valve in any position
except up-side down.

When the burner is installed in the vestibule of  jacketed equipment, it is recommended

that the Automatic Safety Shut-Off Valve be left adjacent to the burner within the vestibule
and the Main Manual Shut-Off Valve be installed outside.

Run full size pipe or tubing from regulator vent openings to outside of building. Refer to

regulator manufactures’s installation instructions. Provide no traps in the vent lines and
terminate away from all doors and windows; also make provisions for keeping rain and
foreign objects from entering the vent piping.

When high supply gas pressure is encountered, as in the case in many industrial plants,

the gas line size can be reduced to allow for a greater pressure drop; however, the size must
be sufficient to deliver burner rating pressure.

CAUTION: High gas pressure supply lines require the proper pressure

reducing regulators. Install a high pressure regulator of the Tight Shut-Off type, sized
for main gas input, upstream of the low pressure regulators.  

The high pressure regulators must be adjustable to 14" W.C. outlet pressure.

When the gas supply line is about to be put into service it must be tested to insure that it

is gas tight. Use air or inert gas under pressure and test with soap and water to locate leaks.

Before gas is turned onto the system, a check must be made to see that there are no open

fittings and to make sure the burner main valve is closed. 

Part 1 

Installation Continued

4

Part 1 Installation

III

Piping

Continued

Natural Gas capacities
shown are for a total
pressure drop of 0.3"W.C.
For 0.5"W.C. pressure drop,
multiply capacity shown by
1.3. For higher permissible
pressure drops, consult
your gas supplier.

Table 2:

Schedule 40 NPT Pipe-Capacity Chart

10

200

400

40

200

450

650

75

150

325

475

20

150

275

Pipe
Size

3/4

1

1 1/4

1 1/2

Natural

Natural

Natural

Natural

100

275

400

Approximate Capacity -MBH

Pipe Length

Type

of Gas

Figure

2:

Typical 

Piping Diagram

Содержание Economite RE4400DS

Страница 1: ...ry to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately phone your gas supplier from another building Follow the gas supplier s instructions If y...

Страница 2: ...ion chamber and to permit burner removal or as recommended by the equipment manufacturer CAUTION In no case should the burner tube be allowed to extend into the chamber because high combustion chamber...

Страница 3: ...ximum firing rate of the burner the gas supply piping must be sized to provide a minimum pressure of 7 0 W C Natural for 400 MBH to the inlet of the combination redundant valve when the burner and all...

Страница 4: ...rop however the size must be sufficient to deliver burner rating pressure CAUTION High gas pressure supply lines require the proper pressure reducing regulators Install a high pressure regulator of th...

Страница 5: ...Do not purge into the gas utilization equipment 3 To purge the gas utilization equipment and chimney of any accumulated gases turn main Manual Gas Cock OFF turn burner power on and set operating cont...

Страница 6: ...r by checking the flue gases with an ORSAT or similar combustion testing instrument The carbon monoxide content should conform to local codes or in their absence to the level specified in the United S...

Страница 7: ...o provide the correct gas flow for the burner Refer to Table 3 for the correct maximum fire manifold pressure settings If the burner lights and then loses the DC micro Amp flame signal it will retry t...

Страница 8: ...r reduce the air vary the alignment between the damper and the inlet ring Minimum air shutter adjustment can be done by adjusting the three 8 18 screws on the inlet ring see Figure 5 To increase or de...

Отзывы: