31
7.0
Operation
7.1
Wireless Input/Output unit Operation
7.1.1 Normal Operation
In its normal state, the LEDs are green (see section 6.2 Wireless Input/Output unit LEDs and
Buttons on page 29).
7.1.2 Button Operation (UL)
Press the button during normal operation to test the attached horn or horn/strobe at its nominal
volume for the duration of the button press.
The horn or horn/strobe returns to its normal state when the button is released. The LEDs
remain in their normal state (green) while the button is pressed.
7.1.3 Button Operation (ULC)
This button has two functions (FOR ULC APPLICATIONS):
Signal Silence:
Press and quickly release the button to silence the signal. This silences the horn locally.
Sound Test:
Press and hold the button to test the attached horn or horn/strobe at its nominal volume for the
duration of the button press.
The horn or horn/strobe returns to its normal state when the button is released. The LEDs
remain in their normal state while the button is pressed.
7.1.4 Button Operation while in Trouble Condition
Pressing the button while the Wireless Input/Output unit is in trouble condition activates the
horn or horn/strobe at its nominal volume for the duration of the button press. The horn or horn/
strobe returns to its normal state when the button is released. The LEDs remain in their
Trouble State while the button is pressed.
7.1.5 Alarm Condition
When the Zone Controller enters alarm condition, it activates the horn or horn/strobe at its
nominal volume. The Wireless Input/Output unit’s LEDs are steady (non-flashing) red. The
alarm condition is cleared with the FACP System Reset Command. Pre-existing trouble
conditions or subsequent trouble conditions do not have any affect on the alarm condition.
7.1.6 Alarm Tones
Continuous temporal or alert alarm codes are available when using input 1 of the Zone
Controller connection to the fire alarm control panel. Connection to all other Zone Controller
inputs other than 1 will be either temporal or continuous. Temporal alarm code is the default.
Alarm codes are changed using the Zone Controller configurator. Two stage is available for
connection to Mircom Fire Alarm panels. DIP switches for the NAC devices shall be set
according to the alarm code required.