Indicators and Controls
6.1
Zone Controller LEDs and Controls (Ancillary for ULC)
Figure 30 Zone Controller LEDs and Controls
6.1.1 Buttons
Reset (Password Protected): Press Reset to
•
reset all Latching, Trouble Conditions.
•
turn OFF Signal Silence.
•
stop and reset all Timers.
•
process inputs as new events.
The Zone Controller will net reset until the Signal Silence Inhibit timer has expired.
Signal Silence (Password Protected): Pressing the Signal Silence button when the Zone
Controller is in Alarm turns on the Signal Silence LED and deactivates any Silenceable
Indicating Circuits. Non-Silenceable Circuits are unaffected. Signals will re-sound uon
any subsequent alarm.
This button does not function during the following:
•
Any configured Signal Silence Inhibit Timer period.
•
If Fire Drill has activated the Indicating Circuits.
Enter, Menu, Cancel, Info:
Use these buttons to navigate the menu on the LCD display.
Signal Silence
LED
Alarm
LED
LCD Display
Trouble
LED
Supervisory
LED
AC
LED
Menu
Cancel
Info
Enter