10
Zone Controller Installation
3.6
DIP Switches
Configure each Zone Controller with both a PAN ID (zone controller panel identification) and
channel ID.
Configure all devices in the same zone with the same PAN ID and channel ID.
Use the lower bank of DIP switches, as shown in Figure 6.
Figure 6
Location of Zone Controller DIP Switches and USB port
3.6.1 Setting the DIP Switches
Use the lower bank of DIP switches to set the PAN ID and channel ID as shown in Figure 7.
See Section 8.0 on page 34 for the list of DIP switch settings.
Figure 7
DIP Switches on the Zone Controller set to Channel ID 19 and PAN ID 1126
Bottom DIP
switches are for
PAN ID and
Channel ID
USB port for
configuration
NOT USED
1
2
4
8
0
1
ON
OFF
3
5
6
7
1-0-0-0-0-0-0-0
1-0-0-0-0-0-0-0
PAN ID
Channel ID