MCS-Bacnet-Router2
REVISION 2
6
Chapter - 2. Quick-Start Guide
This chapter provides the minimum list of steps necessary to setup the MCS-BACNET-ROUTER2
model MCS-BACNET-ROUTER2.
2.1. Hardware Installation and IP Connection
• Connect power, Ethernet, and MS/TP.
•
Connect the Console (Section 8.2.1) and configure the IP address, netmask, and gateway or
connect to the MCS-BACNET-ROUTER2 over the Web interface right away and setup the IP
configuration there.
• In both cases, reboot the MCS-BACNET-ROUTER2 to commit the new IP settings (use corre-
sponding menu item either in console menu or Web interface).
Important!
The default IP address 192.168.1.254 is only set for configuration access. It must be changed in
order to make the device functional.
2.2.
Configuration of the
MCS-BACNET-ROUTER2
• Connect to the MCS-BACNET-ROUTER2 using the new IP address in a Web browser.
•
Click on Config and enter the default administrator password
'loytec4u'
. Note, that older firmware
versions used 'admin' as the password.
•
Click on BACnet Config and setup the BACnet Device Configuration).
•
Click on Port Config and setup the BACnet/IP and BACnet MS/TP port configuration
• If the MCS-BACNET-ROUTER2 should also act as a BBMD, click on BACnet BDT and setup the
Broadcast Distribution Table.
• Reboot the MCS-BACNET-ROUTER2 to commit the changes.
2.3. MS/TP Protocol Analyzer
The MCS-BACNET-ROUTER2 is equipped with a built-in MS/TP protocol capture facility. This facility can be
used for offline logging, which stores a log file on the device, or online remote logging with Wireshark. With
remote capture a Wireshark protocol analyzer on the PC can
capture a live log of the MS/TP channel. For doing
so, the remote capture has to be enabled. See Section 8.3 for more details.
2.4. Reset to Factory Defaults
In case the password of the device has been forgotten you may need to reset the device back to factory
defaults to gain access again. On the MCS-BACNET-ROUTER2 press the service button and power-cycle the
device. Keep the button pressed until the port LEDs illuminate orange permanently. Release the button within
five seconds from that time on to reset the device to factory defaults.