MCS-Bacnet-Router2 

REVISION 2

16

4.3.5 

BACnet Device Configuration

Figure 11 shows the BACnet device configuration page. This configuration page allows setting the 

Device ID

which is the instance part of the Object_Identifier property of the BACnet Device object. The field 

Device 

name 

holds the name of the BACnet device  object (property Object_Name).

Important: 

The device ID and device name must be unique within the BACnet internetwork.

Further, the description and location can be configured. These configuration items correspond to the properties 

Description, and Location respectively of the BACnet Device object. For tuning BACnet application timing 

parameters, set 

APDU timeout

APDU segment timeout

, and 

APDU retry count

. The timeout values are 

entered in seconds allowing decimal notation, e.g. "7.5".

On the settings for BACnet/IP refer to Section 4.2.6. For configuring the MS/TP data link refer to.

Note: 

If this page displays the message "Device communication is disabled via BACnet network!" the device has 

been externally disabled. Reboot the device to activate  communication again.

4.3.6 

BACnet/IP Configuration

The BACnet/IP protocol is available on the Ethernet port. To enable BACnet/IP on the device, select the 

BACnet/IP check box on the Ethernet tab of the port configuration page.

The BACnet/IP protocol settings are displayed in the settings box on the right-hand side as shown in Figure 

12. The 

Network Number 

of the BACnet/IP port must be configured to operate the built-in router. If the 

LIP-ME201 User Manual 

20 

LOYTEC  

Version 4.8 

LOYTEC electronics GmbH 

 

 

Figure 10: FTP server configuration on the Ethernet port. 

4.2.5  BACnet Device Configuration 

Figure 11 shows the BACnet device configuration page.  This configuration page allows 
setting the 

Device ID

, which is the instance part of the Object_Identifier property of the 

BACnet Device object. The field 

Device name

 holds the name of the BACnet device 

object (property Object_Name). 

Important: 

The device ID and device name must be unique within the BACnet internetwork. 

 

Figure 11: BACnet Device Configuration. 

Further, the description and location can be configured. These configuration items 
correspond to the properties Description, and Location respectively of the BACnet Device 
object. For tuning BACnet application timing parameters, set 

APDU timeout

APDU

segment timeout

, and 

APDU retry count

. The timeout values are entered in seconds 

allowing decimal notation, e.g. "7.5". 

On the settings for BACnet/IP refer to Section 4.2.6. For configuring the MS/TP data link 
refer to Section 4.2.7. 

Note: 

If this page displays the message "Device communication is disabled via BACnet network!" 
the device has been externally disabled. Reboot the device to activate communication 
again.  

4.2.6  BACnet/IP Configuration 

The BACnet/IP protocol is available on the Ethernet port. To enable BACnet/IP on the 
device, select the BACnet/IP checkbox on the Ethernet tab of the port configuration page. 

The BACnet/IP protocol settings are displayed in the settings box on the right-hand side as 
shown in Figure 12. The 

Network Number

 of the BACnet/IP port must be configured to 

operate the built-in router. If the BACnet/IP network uses a non-default UDP port number 

LIP-ME201 User Manual 

20 

LOYTEC  

Version 4.8 

LOYTEC electronics GmbH 

 

 

Figure 10: FTP server configuration on the Ethernet port. 

4.2.5  BACnet Device Configuration 

Figure 11 shows the BACnet device configuration page.  This configuration page allows 
setting the 

Device ID

, which is the instance part of the Object_Identifier property of the 

BACnet Device object. The field 

Device name

 holds the name of the BACnet device 

object (property Object_Name). 

Important: 

The device ID and device name must be unique within the BACnet internetwork. 

 

Figure 11: BACnet Device Configuration. 

Further, the description and location can be configured. These configuration items 
correspond to the properties Description, and Location respectively of the BACnet Device 
object. For tuning BACnet application timing parameters, set 

APDU timeout

APDU

segment timeout

, and 

APDU retry count

. The timeout values are entered in seconds 

allowing decimal notation, e.g. "7.5". 

On the settings for BACnet/IP refer to Section 4.2.6. For configuring the MS/TP data link 
refer to Section 4.2.7. 

Note: 

If this page displays the message "Device communication is disabled via BACnet network!" 
the device has been externally disabled. Reboot the device to activate communication 
again.  

4.2.6  BACnet/IP Configuration 

The BACnet/IP protocol is available on the Ethernet port. To enable BACnet/IP on the 
device, select the BACnet/IP checkbox on the Ethernet tab of the port configuration page. 

The BACnet/IP protocol settings are displayed in the settings box on the right-hand side as 
shown in Figure 12. The 

Network Number

 of the BACnet/IP port must be configured to 

operate the built-in router. If the BACnet/IP network uses a non-default UDP port number 

Содержание MCS-BACNET-ROUTER 2

Страница 1: ...tal Solution for all your Control Needs 5580 Enterprise Pkwy Fort Myers FL 33905 Office 239 694 0089 Fax 239 694 0031 www mcscontrols com MCS BACNET ROUTER 2 Installation Reference Guide Revision 2 11 30 2017 ...

Страница 2: ...ent shall be published used reproduced transmitted or disclosed to others out side your organization without the prior expressed written consent of Micro Control Systems Inc This document and the information contained herein shall be treated as proprietary Reasonable provisions shall be provided to ensure that this information remains proprietary by your employees agents and other personnel that m...

Страница 3: ... Mounting 8 3 4 LED signals 8 3 4 1 Power LED 8 3 4 2 Status LED 8 3 4 3 MSTP Activity LED 8 3 4 4 Ethernet Link LED 8 3 4 5 Ethernet Activity LED 8 3 4 6 BACnet IP LED 8 3 4 7 BBMD LED 9 3 5 Status Button 9 3 6 Wiring 10 Chapter 4 Web Interface 11 4 1 Device Information and Account Management 11 4 2 Login and Passwords 12 4 3 Device Configuration 13 4 3 1 System Configuration 13 4 3 2 Backup and ...

Страница 4: ...T Broadcast Distribution Table B IP BACnet over IP this is a BACnet data link layer DHCP Dynamic Host Configuration Protocol DNS Domain Name System DST Daylight Saving Time FD Foreign Device FTP File Transfer Protocol GMT Greenwich Mean Time IP Internet Protocol MAC Media Access Control MS TP Master Slave Token Passing this is a BACnet data link layer NAT Network Address Translation NTP Network Ti...

Страница 5: ...s a BACnet time master and a BACnet MS TP slave proxy The MCS BACNET ROUTER2 also provides additional features such as optional write protection of the BDT a BACnet IP access control list and a simple BBMD communications test to troubleshoot the network The MS TP port supports remote Wireshark packet capture for troubleshooting the MS TP channel 1 1 1 Scope This document covers MCS BACNET ROUTER2 ...

Страница 6: ... as the password Click on BACnet Config and setup the BACnet Device Configuration Click on Port Config and setup the BACnet IP and BACnet MS TP port configuration If the MCS BACNET ROUTER2 should also act as a BBMD click on BACnet BDT and setup the Broadcast Distribution Table Reboot the MCS BACNET ROUTER2 to commit the changes 2 3 MS TP Protocol Analyzer The MCS BACNET ROUTER2 is equipped with a ...

Страница 7: ... are encoded using Code 128 An additional label is also supplied with the MCS BACNET ROUTER2 for documentation purposes Version 4 8 LOYTEC electronics GmbH 3 Hardware Installation 3 1 Enclosure The LIP ME201 enclosure is 107 mm wide for DIN rail mounting following DIN 43 880 see Figure 1 4 5 6 Status Button and LED 105 off on 1 2 3 4 5 6 7 DIP Switch 60 55 Serial Number Order Number 85 Console Con...

Страница 8: ...flects a state Flicker is for 25 ms when there is activity on the MS TP data link layer Behavior Description Comment GREEN permanently flicker off Multi Master token ok flicker when traffic Normal condition on a multi master MS TP network ORANGE flicker Sole master flicker when traffic Normal condition on a single master MS TP network RED permanent flicker GREEN Token lost state flicker when trans...

Страница 9: ...ory defaults over the console user interface 1 1 DIP Switch Settings The DIP switch assignment for the MCS BACNET ROUTER2 is shown in Table 2 Please leave all switches at default state DIP Switch Function Factory Default 1 Must be OFF OFF 2 Must be OFF OFF 3 Must be ON ON 4 Must be OFF OFF 5 Must be OFF OFF 6 Must be OFF OFF 7 Must be OFF OFF Table 2 DIP Switch Settings for MCS BACNET ROUTER2 1 2 ...

Страница 10: ...ics GmbH 16 17 Power Supply 12 35 VDC or 12 24 VAC 10 Do not connect terminal 17 to earth ground Table 3 LIP ME201 Terminals 3 8 Wiring If BACnet over MS TP is enabled the MS TP network segment must be properly terminated with an LT 04 network terminator connected at each of the two ends of the segment media Important When using 2 wire MS TP earth ground must be connected to both terminal 15 and 1...

Страница 11: ...ual IP address 6 Then open your Web browser and type in the default IP address 192 168 1 254 7 The device information page should appear as shown in Figure 3 The device information page shows information about the MCS BACNET ROUTER2 and the current firmware version It also contains operational parameters such as free memory system temperature and supply voltage LIP ME201 User Manual 15 LOYTEC Figu...

Страница 12: ...e information page shows information about the LIP ME201 and the current firmware version It also contains operational parameters such as free memory system temperature and supply voltage Click through the menus on the left hand side to become familiar with the different screens If you click on Config in the left menu you will be asked to enter the administrator password in order to make changes t...

Страница 13: ...urce It is specified as the offset to GMT in hours and minutes e g Vienna Austria is 01 00 New York USA is 06 00 For setting the daylight saving time DST predefined choices are offered for Europe and USA Canada DST can be switched off completely by choosing none or set manually for other regions In that case start and end date of DST must be entered in the fields below The next section on the page...

Страница 14: ...the label e g Port 1 Port 2 Ethernet a corresponding configuration tab is provided by the Web UI An example is shown in Figure 8 Each port tab contains a selection of available communication protocols By selecting a checkbox or radio button the various protocols can be enabled or disabled on the communication port Some ports allow exclusive protocol activation only other ports e g the Ethernet por...

Страница 15: ...rd protocols that are bound to the Ethernet interface are FTP Telnet and HTTP Web server By deselecting the checkbox those protocols can be individually disabled The standard UDP TCP ports can be changed in the respective protocol settings An example for the FTP server is shown for FTP in Figure 10 The FTP server is used for instance to update the firmware see Section 7 1 Note that HTTP for the We...

Страница 16: ...out values are entered in seconds allowing decimal notation e g 7 5 On the settings for BACnet IP refer to Section 4 2 6 For configuring the MS TP data link refer to Section 4 2 7 Note If this page displays the message Device communication is disabled via BACnet network the device has been externally disabled Reboot the device to activate communication again 4 2 6 BACnet IP Configuration The BACne...

Страница 17: ...ACnet IP Configuration In the field BACnet IP mode the operation mode of the device is selected Device Default In this mode the device operates as a regular BACnet IP device on the local network without other advanced features Foreign Device FD In this mode the device registers at an existing BBMD in the BACnet IP network as a foreign device It is used if the device is located as a single BACnet I...

Страница 18: ...e setting for MS TP max master Decreasing the default value 127 of MS TP max master may reduce latency on the MS TP bus It is strongly recommended to leave the MS TP max info frames and the MS TP max master configuration options at their default settings In any case the MS TP max master number must be high enough to include the highest MS TP node number of all masters on the channel Slave devices ...

Страница 19: ...MCS Bacnet Router2 REVISION 2 19 ...

Страница 20: ...Providing HVAC R Control Solutions Worldwide 5580 Enterprise Pkwy Fort Myers FL 33905 Office 239 694 0089 Fax 239 694 0031 www mcscontrols com ...

Отзывы: