MCS-Bacnet-Router2 

REVISION 2

12

4.2. 

Login and Passwords

Click through the menus on the left hand side to become familiar with the different screens. If you click on 

Config 

in the left menu, you will be asked to enter the administrator password in order to make changes to 

the settings as shown in Figure 4. Enter the default administrator password ‘loytec4u’ and select 

Login

. Note, 

that previous firmware versions used ‘admin’ as the default password.

The Config menu opens. Click on 

Passwords 

in the Config menu, which opens the password configuration 

page as shown in Figure 5. The device has three user accounts: (1) 

guest 

allows the user to view certain 

information only, e.g., the device info page. By  default the guest user has no password. (2) 

operator 

is able 

to read more sensible information such as calendar data. (3) 

admin 

has full access to the device and can 

make changes to its configuration. Note that the user accounts are also used to log on to the FTP and Telnet 

server.

Please change the administrator password in order to protect yourself from unwanted configuration changes 

by anyone else. To do so, select the 

admin 

account in the drop- down box and enter the new password. 

If the administrator password is left empty, password protection is turned off and everyone can access the 

MCS-BACNET-ROUTER2 without entering a password. Click on 

Change password 

to activate the change.

LIP-ME201 User Manual 

15 

LOYTEC  

Version 4.8 

LOYTEC electronics GmbH 

 

 

Figure 3: Device Information Page. 

The device information page shows information about the LIP-ME201 and the current 
firmware version. It also contains operational parameters, such as free memory, system 
temperature and supply voltage.  

Click through the menus on the left hand side to become familiar with the different screens. 
If you click on 

Config

 in the left menu, you will be asked to enter the administrator 

password in order to make changes to the settings as shown in Figure 4. Enter the default 
administrator password ‘loytec4u’ and select 

Login

. Note, that previous firmware versions 

used ‘admin’ as the default password. 

 

Figure 4: Enter ‘loytec4u’ as the default administrator password. 

The Config menu opens. Click on 

Passwords

 in the Config menu, which opens the 

password configuration page as shown in Figure 5. The device has three user accounts: (1) 

guest

 allows the user to view certain information only, e.g., the device info page. By 

default the guest user has no password. (2) 

operator

 is able to read more sensible 

information such as calendar data. (3) 

admin

 has full access to the device and can make 

changes to its configuration. Note that the user accounts are also used to log on to the FTP 
and Telnet server. 

LIP-ME201 User Manual 

16 

LOYTEC  

Version 4.8 

LOYTEC electronics GmbH 

 

 

Figure 5: Password Configuration Screen. 

Please change the administrator password in order to protect yourself from unwanted 
configuration changes by anyone else. To do so, select the 

admin

 account in the drop-

down box and enter the new password. If the administrator password is left empty, 
password protection is turned off and everyone can access the LIP-ME201 without entering 
a password. Click on 

Change password

 to activate the change. 

4.2  Device Configuration 

The device configuration pages allow viewing and changing the device settings of the LIP-
ME201. Here are some general rules for setting IP addresses, port numbers, and time 
values: 

An empty IP address field disables the entry. 

An empty port number field sets the default port number. 

An empty time value field disables the time setting. 

4.2.1  System Configuration 

The system configuration page is shown in Figure 6. This page allows configuring the 
device’s system time and other system settings. The 

TCP/IP Configuration

 link is a 

shortcut to the Ethernet port configuration. Follow that link to change the IP settings of the 
device. 

The time sync source can be set to 

auto

manual

NTP

BACnet

. In the 

auto

 mode, the 

device switches to the first external time source that is discovered. Possible external time 
sources are NTP, BACnet. The option 

manual

 allows setting the time manually in the 

fields 

Local Time

 and 

Local Date

. In 

manual

 mode, the device does not switch to an 

external time source. Note, that if 

NTP

 is selected, the NTP servers have to be configured 

on the IP Configuration page (see Section 4.2.4). 

The time zone offset must be defined independently of the time source. It is specified as the 
offset to GMT in hours and minutes (e.g., Vienna/Austria is +01:00, New York/USA is 
-06:00). For setting the daylight saving time (DST) predefined choices are offered for 
Europe and USA/Canada. DST can be switched off completely by choosing 

none

 or set 

manually for other regions. In that case, start and end date of DST must be entered in the 
fields below. 

Содержание MCS-BACNET-ROUTER 2

Страница 1: ...tal Solution for all your Control Needs 5580 Enterprise Pkwy Fort Myers FL 33905 Office 239 694 0089 Fax 239 694 0031 www mcscontrols com MCS BACNET ROUTER 2 Installation Reference Guide Revision 2 11 30 2017 ...

Страница 2: ...ent shall be published used reproduced transmitted or disclosed to others out side your organization without the prior expressed written consent of Micro Control Systems Inc This document and the information contained herein shall be treated as proprietary Reasonable provisions shall be provided to ensure that this information remains proprietary by your employees agents and other personnel that m...

Страница 3: ... Mounting 8 3 4 LED signals 8 3 4 1 Power LED 8 3 4 2 Status LED 8 3 4 3 MSTP Activity LED 8 3 4 4 Ethernet Link LED 8 3 4 5 Ethernet Activity LED 8 3 4 6 BACnet IP LED 8 3 4 7 BBMD LED 9 3 5 Status Button 9 3 6 Wiring 10 Chapter 4 Web Interface 11 4 1 Device Information and Account Management 11 4 2 Login and Passwords 12 4 3 Device Configuration 13 4 3 1 System Configuration 13 4 3 2 Backup and ...

Страница 4: ...T Broadcast Distribution Table B IP BACnet over IP this is a BACnet data link layer DHCP Dynamic Host Configuration Protocol DNS Domain Name System DST Daylight Saving Time FD Foreign Device FTP File Transfer Protocol GMT Greenwich Mean Time IP Internet Protocol MAC Media Access Control MS TP Master Slave Token Passing this is a BACnet data link layer NAT Network Address Translation NTP Network Ti...

Страница 5: ...s a BACnet time master and a BACnet MS TP slave proxy The MCS BACNET ROUTER2 also provides additional features such as optional write protection of the BDT a BACnet IP access control list and a simple BBMD communications test to troubleshoot the network The MS TP port supports remote Wireshark packet capture for troubleshooting the MS TP channel 1 1 1 Scope This document covers MCS BACNET ROUTER2 ...

Страница 6: ... as the password Click on BACnet Config and setup the BACnet Device Configuration Click on Port Config and setup the BACnet IP and BACnet MS TP port configuration If the MCS BACNET ROUTER2 should also act as a BBMD click on BACnet BDT and setup the Broadcast Distribution Table Reboot the MCS BACNET ROUTER2 to commit the changes 2 3 MS TP Protocol Analyzer The MCS BACNET ROUTER2 is equipped with a ...

Страница 7: ... are encoded using Code 128 An additional label is also supplied with the MCS BACNET ROUTER2 for documentation purposes Version 4 8 LOYTEC electronics GmbH 3 Hardware Installation 3 1 Enclosure The LIP ME201 enclosure is 107 mm wide for DIN rail mounting following DIN 43 880 see Figure 1 4 5 6 Status Button and LED 105 off on 1 2 3 4 5 6 7 DIP Switch 60 55 Serial Number Order Number 85 Console Con...

Страница 8: ...flects a state Flicker is for 25 ms when there is activity on the MS TP data link layer Behavior Description Comment GREEN permanently flicker off Multi Master token ok flicker when traffic Normal condition on a multi master MS TP network ORANGE flicker Sole master flicker when traffic Normal condition on a single master MS TP network RED permanent flicker GREEN Token lost state flicker when trans...

Страница 9: ...ory defaults over the console user interface 1 1 DIP Switch Settings The DIP switch assignment for the MCS BACNET ROUTER2 is shown in Table 2 Please leave all switches at default state DIP Switch Function Factory Default 1 Must be OFF OFF 2 Must be OFF OFF 3 Must be ON ON 4 Must be OFF OFF 5 Must be OFF OFF 6 Must be OFF OFF 7 Must be OFF OFF Table 2 DIP Switch Settings for MCS BACNET ROUTER2 1 2 ...

Страница 10: ...ics GmbH 16 17 Power Supply 12 35 VDC or 12 24 VAC 10 Do not connect terminal 17 to earth ground Table 3 LIP ME201 Terminals 3 8 Wiring If BACnet over MS TP is enabled the MS TP network segment must be properly terminated with an LT 04 network terminator connected at each of the two ends of the segment media Important When using 2 wire MS TP earth ground must be connected to both terminal 15 and 1...

Страница 11: ...ual IP address 6 Then open your Web browser and type in the default IP address 192 168 1 254 7 The device information page should appear as shown in Figure 3 The device information page shows information about the MCS BACNET ROUTER2 and the current firmware version It also contains operational parameters such as free memory system temperature and supply voltage LIP ME201 User Manual 15 LOYTEC Figu...

Страница 12: ...e information page shows information about the LIP ME201 and the current firmware version It also contains operational parameters such as free memory system temperature and supply voltage Click through the menus on the left hand side to become familiar with the different screens If you click on Config in the left menu you will be asked to enter the administrator password in order to make changes t...

Страница 13: ...urce It is specified as the offset to GMT in hours and minutes e g Vienna Austria is 01 00 New York USA is 06 00 For setting the daylight saving time DST predefined choices are offered for Europe and USA Canada DST can be switched off completely by choosing none or set manually for other regions In that case start and end date of DST must be entered in the fields below The next section on the page...

Страница 14: ...the label e g Port 1 Port 2 Ethernet a corresponding configuration tab is provided by the Web UI An example is shown in Figure 8 Each port tab contains a selection of available communication protocols By selecting a checkbox or radio button the various protocols can be enabled or disabled on the communication port Some ports allow exclusive protocol activation only other ports e g the Ethernet por...

Страница 15: ...rd protocols that are bound to the Ethernet interface are FTP Telnet and HTTP Web server By deselecting the checkbox those protocols can be individually disabled The standard UDP TCP ports can be changed in the respective protocol settings An example for the FTP server is shown for FTP in Figure 10 The FTP server is used for instance to update the firmware see Section 7 1 Note that HTTP for the We...

Страница 16: ...out values are entered in seconds allowing decimal notation e g 7 5 On the settings for BACnet IP refer to Section 4 2 6 For configuring the MS TP data link refer to Section 4 2 7 Note If this page displays the message Device communication is disabled via BACnet network the device has been externally disabled Reboot the device to activate communication again 4 2 6 BACnet IP Configuration The BACne...

Страница 17: ...ACnet IP Configuration In the field BACnet IP mode the operation mode of the device is selected Device Default In this mode the device operates as a regular BACnet IP device on the local network without other advanced features Foreign Device FD In this mode the device registers at an existing BBMD in the BACnet IP network as a foreign device It is used if the device is located as a single BACnet I...

Страница 18: ...e setting for MS TP max master Decreasing the default value 127 of MS TP max master may reduce latency on the MS TP bus It is strongly recommended to leave the MS TP max info frames and the MS TP max master configuration options at their default settings In any case the MS TP max master number must be high enough to include the highest MS TP node number of all masters on the channel Slave devices ...

Страница 19: ...MCS Bacnet Router2 REVISION 2 19 ...

Страница 20: ...Providing HVAC R Control Solutions Worldwide 5580 Enterprise Pkwy Fort Myers FL 33905 Office 239 694 0089 Fax 239 694 0031 www mcscontrols com ...

Отзывы: