©2020 Micro-Air Corp. 

 

 

 

 

 

 

 

 

 

Rev 1.5 

7.

 

Is the black wire from EasyStart connected to the compressor common winding

?  

Step 4 identified the compressor wiring cover and run winding wire. Identify the 

compressor “C” winding wire color using the same steps in step 4. Follow the wire through 

the wire harness to the connection at the contactor, relay or circuit board. Verify that the 
Black wire from EasyStart is connected somewhere along that wire or on the contactor for 
larger systems.  

If steps 1 to 7 do not yield a solution, go to th

Checking Trouble Lights

 section and check the 

state of EasyStart. 

Troubleshooting Generator Only Problems 

 

If your system works as expected on utility power and does not start or starts and shuts off on 

generator power, this section is the place to start.  

Starting then shutting off  

This could mean it runs for a few seconds or 10 minutes or more before it shuts off.  Be sure 

the thermostat did not turn off the compressor then read the following: 

EasyStart takes itself out of the circuit after the start is complete. It does remain active 

monitoring for faults that could indicate a generator overload. If it detects these faults, 
EasyStart will shut down the compressor and wait 5 minutes before restarting. These faults are 
caused by the power source and not by EasyStart. Some common causes of generator problems 
are: 

 

Obstructed air or fuel filters, bad fuel, dirty fuel delivery systems. 

 

Excessive loading on generator: Small generators like 2000-watt units are often running 
close to maximum capacity to run an Air Conditioner. Auxiliary loads like battery 
chargers or converters, refrigerators, and water heaters can be enough to cause a 
generator overload. 

 

Elevation: Motors in generators are calibrated to meet emissions standards at sea level. 
As elevation rises the motors run richer and power output drops. Generators operated 
above 5000 feet sometimes need to be recalibrated for proper operation. 

 

Temperature: High temperatures cause an increase in refrigerant pressure and higher 
compressor current. Be sure Air conditioner vents and fins are clear of dirt and debris. 
Verify using a clamp on current meter that the air conditioner is not drawing more than 
the generators rated power output. 

 

 

Содержание EASYSTART

Страница 1: ...ine if EasyStart is the cause of the problem This document is separated into sections that guide troubleshooting from new installations to existing systems Understanding the short cycle timer is important to troubleshooting Read that section then jump to the section that applies to your situation Note Some testing in this document involves testing with live AC utility power This power can cause se...

Страница 2: ... a generator 7 Troubleshooting Previously Working Systems 8 Checking Trouble Lights 8 No trouble lights on 8 Trouble lights are on 9 Trouble light definitions 9 Unexpected current 9 Over current 9 Power interruption Short cycle timer 9 Open compressor overload 9 Stall 9 Wrong line voltage 10 No signal from start winding 10 Testing for a no signal problem 10 Additional power interruption fault info...

Страница 3: ...t Most times installers have already checked the wiring several times by the time they read this This section is a comprehensive look at each connection and what to look for to help find what may have been missed during installation Please take the time to consider this a fresh look at what you have already checked 1 Are you powered by a power source that will normally start the compressor We reco...

Страница 4: ... stamp a letter on the compressor housing to indicate the connections Use these markings to identify the color wire your compressor uses for the R connection This wire must connect to the brown wire from EasyStart and is usually white in many installations Follow the wire from the compressor to the electrical box and verify that is connects to the brown wire from EasyStart in the electrical box Th...

Страница 5: ...se wires connect to start components that are no longer used and must be removed Follow the wires to their end connections If the connection is a spade style connection to a run capacitor or circuit board simply remove the wire If the wire goes to a PTC device then the device will have two wires going into it Follow the second wire and disconnect it from its connector You can remove the PTC comple...

Страница 6: ...cuit after the start is complete It does remain active monitoring for faults that could indicate a generator overload If it detects these faults EasyStart will shut down the compressor and wait 5 minutes before restarting These faults are caused by the power source and not by EasyStart Some common causes of generator problems are Obstructed air or fuel filters bad fuel dirty fuel delivery systems ...

Страница 7: ... on a reliable source that will run the AC for long enough to get a steady reading That reading should be below the continuous duty rating of your generator Does not run at all on a generator If it does not run at all on a generator but runs fine on shore power here are some possible causes 1 Wiring is not correct Usually the original start components were left connected although other wiring mist...

Страница 8: ... start will occur right away Next have a helper apply power while you are touching the compressor Be sure the thermostat is set to turn in the compressor The fan should start and the compressor should operate a few seconds after the fan If the compressor fails to start then look at the trouble lights No trouble lights on If no lights are on or you are getting a stalled compressor indication power ...

Страница 9: ...e device or the maximum value calculated during the learning process In many cases re learning EasyStart can clear this problem This can also be caused by a failing compressor poor condenser flow or bad run capacitor Power interruption Short cycle timer In addition to the short cycle delay this indication provides it also provides indication of a short duration power interruption Compressors will ...

Страница 10: ...rify there is continuity from the black wire to the orange wire at the wire connection points This connection will give only the very low resistance of the common to start winding connection when it is properly connected The flow of this path is down the orange EasyStart wire to the run capacitor Through the capacitor terminal to the start winding Through the start winding wire to the start windin...

Страница 11: ...ption Inverter generators will commonly reduce the output if the generators motor cannot keep up This keeps the motor from stalling but also slows the air conditioner which will trip the breaker or overload when the generator resumes supplying power Be sure all the loads are off in the RV when operating your air conditioner on a limited power source Additional help for generator related issues can...

Отзывы: