OPERATING INSTRuCTIONS

1. 

STOP!

 Read the safety information label.

2.  Make sure the manual shutoff valve is fully open.

3.  This gas log set is equipped with an ignition device (piezo) which automatically lights the pilot. If piezo 

ignitor does not light the pilot, refer to instructions for 

Match Lighting Instructions, Page 30.

4.  Turn gas control knob clockwise  to the OFF position and turn ON/OFF switch to OFF position.

5.  Wait (5) minutes to clear out any gas. Then smell for gas, including near the loor. If you smell gas, 

STOP! 

Follow the instructions under 

What To Do If You Smell Gas, Page 30.

6.  From OFF position, turn the gas control knob counterclockwise 

  to IGN position. Push in control knob 

for 5 seconds. 

NOTE: If you are running the heater for the irst time, it may be necessary to press 

in the control knob for 30 seconds or longer to allow air to bleed out of the gas piping. 

7.  With the control knob pushed in, push in and release the piezo ignitor button to light the pilot.
8.  Continue pushing the control knob in for a further 60 seconds to prevent the lame detector from shutting 

off the gas while the probe is warming up. Release the control knob.

9.  Turn gas control knob counterclockwise 

 to the ON position.

10. After the pilot has been lit for one minute, the burner can be turned on.

a.  Slide the three (3) position button on the remote receiver to the ON position and the main gas lame 

should ignite in the Max. Height Setting.

b.  Slide the button to OFF and the main gas lame should extinguish.

c.  Slide the button to RS (the center position), press the ON button on the handheld transmitter to turn 

the system ON. The main gas lame should ignite in the Max Height Setting.

d.  Press the OFF button to decrease lame height. Press the OFF button twice to lower lame level. Press 

the OFF button three times to turn main burner OFF.

11. If the gas logs will not operate, follow the instructions To Turn Off Gas To Heater below and call your service 

technician or gas supplier.

Figure 35 - Pilot 

 Millivolt CONTROL LIGHTING INSTRUCTIONS 

 

TO TURN OFF GAS TO HEATER

 

  1.  Turn control knob clockwise 

 to OFF position to completely shut off the heater.

  2.  If applicable: Turn ON/OFF switch to OFF position and/or set thermostat (if present) to lowest setting.

  3.  If applicable: Turn off all electric power to the heater.

Содержание MJ27NR

Страница 1: ...WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow...

Страница 2: ...11 Floor Clearance 16 Fireplace Preparation 17 Installing Vented Applications 18 Connecting the Gas 19 Checking Gas Pressure 20 Millivolt 20 Electrical Wiring Millivolt 21 Connecting Remote Receiver...

Страница 3: ...ce OWNER Please retain these instructions for future reference IMPORTANT Read these instructions carefully before installing or trying to operate this vent free gas heater 8 CARBON MONOXIDE POISONING...

Страница 4: ...and will disappear with continued use 20 Input ratings are shown in BTU per hour and are for elevations up to 2 000 feet For elevations above 2 000 feet input ratings should be reduced 4 percent for...

Страница 5: ...gile handle with care CAUTION Carefully inspect the contents for shipping damage If any parts are missing or damaged immediately inform the dealer from whom you purchased the appliance Do not attempt...

Страница 6: ...control has three 3 positions OFF All gas to the gas logs is shut off at the valve IGN Valve position to light maintain a standing pilot ON Valve position to turn ON OFF log set with remote switch the...

Страница 7: ...ces installed in that space An unconined space is deined as a space whose volume is not less than 50 cubic feet per 1 000 BTU per hour 4 8 m3 per kw of the aggregate input rating of all appliances ins...

Страница 8: ...etween the two rooms the calculation would be based only on the room with the heater BTU hr 151 2 x 12 x 8 x 1000 29760 BTU hr 50 GENERAL INSTALLATION INFORMATION Figure 1 Example of a Large Room with...

Страница 9: ...nted Room Heaters per IAS Requirement No 2 97 ANSI Z21 91 2001 typically referred to as a Universal Firebox as long as irebox hearth dimensions meet the minimum hearth dimensions shown below Figure 2...

Страница 10: ...actory brick may be used to line the loor of the ireplace in order to raise the height of the gas log set in relation to a restrictive barrier If the unit is raised the minimum height dimension listed...

Страница 11: ...ions shown in Figures 4 through 11 and deined in the ireplace manufacturer s instructions are minimum clearances to maintain when installing this heater Left and right clearances are determined when f...

Страница 12: ...st 1 2 thick Sheet metal should not be installed onto combustible material IMPORTANT If you cannot meet these minimum clearances you must operate the heater with chimney lue damper open Refer to Insta...

Страница 13: ...E B Heat Resistant Material Heights and Mantel Location Heat Resistant Requirements for Safe Installation with Wood Material Mantel Shelf or Other Combustible Projection Measurement MJ27 12 or more Ho...

Страница 14: ...aximum of 6 at a minimum of 141 2 above the opening 10 12 8 6 21 2 8 141 2 185 8 221 2 26 Heat Resistant Material Hood Heater in Fireplace or Firebox FP1999 Figure 8 Minimum Mantel Clearance with No H...

Страница 15: ...EIGHT REQUIREMENTS Figure 9 is an example of an unsafe mantel instal lation This mantel projects 4 at 8 above the opening exceeding the maximum acceptable distance of 21 2 The mantel also projects 7 a...

Страница 16: ...must be maintained from the top surface of carpeting tile etc Figure 10 OR The gas log heater may be installed nearer to the loor if a minimum of 14 of noncombustible material such as slate or marble...

Страница 17: ...heat resistant sealant Do not seal the chimney lue damper INSTALLING vENTED APPLICATIONS Manual and Millivolt controlled gas logs may be installed as a vented decorative log set in compliance with ANS...

Страница 18: ...s essential to prevent any movement of the gas logs and controls during operation Figure 13 Secure Heater to Floor of Fireplace Firebox Screw Anchor Hole Screw WARNING You must secure the gas log heat...

Страница 19: ...ns that the Pressure Tapping Point May Be Installed CAUTION ChECk GAS TYPE The gas supply must be the same as stated on the heater s rating plate If the gas supply is different DO NOT INSTALL ThE hEAT...

Страница 20: ...captured screw counter clockwise two or three turns and then place tubing to pressure gauge over test point Use test point OUT closest to control knob After taking pressure reading be sure and turn ca...

Страница 21: ...ation gas control ThAT DOES NOT REquIRE 110 vAC TO OPER ATE Figure 16 Wiring Diagram CAUTION Label all wires prior to disconnection when servicing controls wiring errors can cause improper and dangero...

Страница 22: ...heck B Reading Thermostat contacts OPEN Main burner OFF 1 Check gas pressure to the unit If gas pressure is within minimum and maximum on data plate then check pilot voltage 500 Millivolts minimum If...

Страница 23: ...wash your hands gently with soap and water to remove any traces of ibers WARNING The positioning of the logs is critical to the safe and clean operation of this heater Sooting and other problems may...

Страница 24: ...e 21 Log 2 LG555 Figure 22 Install Log 2 3 Place log 2 at an angle across the burner by setting the log over the two pins located on top of the burner Figure 22 4 Place log 3 at an angle over log 2 to...

Страница 25: ...Place log 5 by matching the rectangular notch on the bottom of the log with the rect angular protrusion on log 2 Set the notch on the bottom of this log over the very far left tong on the grate Figur...

Страница 26: ...nt logs where they can be seen Try to avoid stacking these embers on top of each other Use smaller stringier strands for maximum effect Use as much as needed until desired effect is achieved Flickerin...

Страница 27: ...ll adjust left to right to center equally in ireplace PLACING ThE DECORATIvE ROCk Bracket FP2012 Figure 29 Attach Bracket to Andiron Figure 30 Attach Andirons to Grate FP2013 CAUTION DO NOT sprinkle v...

Страница 28: ...dition periodically check the lames visually during operation ChECkING ThE PILOT FLAME The pilot lame must always be present when the heater is in operation It should just touch the top of the thermoc...

Страница 29: ...During manufacturing fabricating and shipping various components of this appliance are treated with certain oils ilms or bonding agents These chemicals are not harmful but may produce annoying smoke...

Страница 30: ...all the ire department C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it Call a qualiied service technici...

Страница 31: ...to prevent the lame detector from shutting off the gas while the probe is warming up Release the control knob 9 Turn gas control knob counterclockwise to the ON position 10 After the pilot has been li...

Страница 32: ...ake holes clean will result in sooting and poor combus tion Inspect and clean all burner ports Inspect ODS pilot for operation and accumulation of lint at air intake holes Verify lame pattern and log...

Страница 33: ...2 Contact local gas company 3 ODS pilot is partially clogged 3 Clean ODS pilot 4 Defective Thermopile 4 Check wire connections Check output should be 500 Millivolts across TH TP and TP Terminals with...

Страница 34: ...is too small 2 Burner oriice diameter is too small 3 Inlet gas pressure is too low 3 Inlet gas pressure is too low Burner backires during combustion 1 Manifold pressure is too low 1 Contact local gas...

Страница 35: ...egulator 1 14D0469 7 Thermostatic ON OFF 1 RCSIT RCSIT Flame Height Adj 1 Remote Control 8 Injector 1 70D0064 20H2084 9 Andiron Kit not shown 1 FAI135 FAI135 REPLACEMENT PARTS ARE AVAILABLE THROUGH YO...

Страница 36: ...6 Log 6 1 75D0541 7 Log 7 1 75D0542 8 Log 8 1 86D0019 LOGS REPLACEMENT PARTS LIST REPLACEMENT PARTS ARE AVAILABLE THROUGH YOUR RETAILER Failure to position the parts in accordance with these diagrams...

Страница 37: ...7 feet above inished grade in the area of the venting including but not limited to decks and porches the following requirements shall be satisied 1 INSTALLATION OF CARBON MONOXIDE DETECTORS At the tim...

Страница 38: ...38 86D0024 NOTES...

Страница 39: ...fetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 irebox burner assembly da...

Страница 40: ...OCTOBER 2008 86D0024 Rev 1 MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Отзывы: