FLUE HOOD ASSEMBLY
2.7
Dismantle the counterflange supplied on the flow port, install the flow elbow pipe inserting
the relevant gasket provided and tighten nuts and bolts securely.
Locate the flue hood on the boiler and secure the rear seal plate using the screws provided.
DRAUGHT DIVERTOR ASSEMBLY
2.8
Secure the four fixing brackets on the top side of the draught divertor tightening the self-
tapping screws (brackets and screws provided).
Locate the draught divertor at the highest point on the studs, fixing it on to the flue hood by
tightening securely the stud and nut fixings.
CHIMNEY CONNECTION
2.9
Size and material of non-flexible flue pipe between boiler and chimney should be in accor-
dance with the Regulations in force.
GAS ASSEMBLY
2.10
The gas burner(s) assembly is supplied in a separate carton.
All REGENCY 4 MODULEK boilers are equipped with two gas valves and two burners.
GAS ASSEMBLY FOR BOILER MODELS REGENCY 4 MODULEK 152-272
-
Secure the two brass spacers (using
the hexagonal key 17 mm provided)
on the screwed pivots positioned half
the height of rear plate (nut should be
removed and kept to fix the apron).
-
Secure the aprons (6) to the front and
rear plates using the stud and nut fi-
xings (both aprons are delivered with
the casing in a separate carton).
-
Insert the two multi-bar burners into
the combustion chamber and secure
them to boiler block using the four
side brackets (1).
-
Insert the bulb of the thermometer into the front thermostat pocket and secure it with the
retaining clip provided.
-
Unscrew and free the facia panel from the bracket (7); secure the front apron to the
bracket (7) using the three self-tapping screws F 4,2 x 9,5 (provided) and tighten again
the facia panel to same bracket (7).
-
Secure the White box (Gewiss) containing the rear ionisation controller to the rear apron
(position S) using the self-tapping screws ø 4,2 x 9,5 (provided).
-
Insert the four bulbs of the thermostats into the rear thermostat pocket and secure them
with the retaining clip provided.
-
Secure the gas feed pipe (3) to the side brackets (4) and join it to the gas assembly tight-
ening the two connecting nuts (gaskets are provided).
-
Secure the two pilot burners (5) to the relevant front cast iron plates (to facilitate the
operation it may be necessary to temporarily slacken the pilot gas tube connections).
-
Connect rear electrodes to the ignition and flame detection cables of the control panel.
-
Any disturbed or newly made gas connections must be later tested for soundness.
S
12