Detailed recommendations for the flue are detailed in BS6644 and IM/11. The following notes are
intended for your guidance.
The area of the flue serving the boiler must be not less than the area boiler flue outlet.
Nominal flue pipe diameters between the boiler and chimney should be in accordance with the fol-
lowing table:

REGENCY 4 MODULEK -152

300 mm

(12”)

REGENCY 4 MODULEK -169

300 mm

(12”)

REGENCY 4 MODULEK -186

300 mm

(12”)

REGENCY 4 MODULEK -203

300 mm

(12”)

REGENCY 4 MODULEK -220

300 mm

(12”)

REGENCY 4 MODULEK -237

350 mm

(14”)

REGENCY 4 MODULEK -255

350 mm

(14”)

REGENCY 4 MODULEK -272

350 mm

(14”)

Flue pipes and fittings should be constructed from aluminium, stainless steel or acid resistant vi-
treous enamel lined cast iron. Any double walled flue pipe, must be acceptable to British Gas.
Chimneys should be lined with non-porous acid resistant material in accordance with BS5854,
such as stainless steel flexible flue liner or similar British Gas approved material. The internal
diameter of the liner must not be less than the recommended flue pipe and the number of joints
should be kept to a minimum. Any joints between the flexible liner and the flue pipe from the boi-
ler should be effected by means of a purpose built adaptor plate. Existing flues should be tho-
roughly swept before use and any register plates, restrictor plates or dampers should be removed.
If the flue is not fitted with a terminal, then the flue outlet should be fitted with a wire mesh to pro-
tect against blockage. The terminal should not be sited adjacent to any opening window, air vent,
or other ventilation opening and should be situated at least 1 m above the roof surface. All should
be in accordance with BS6644.

FLUE SYSTEM

2.3

AIR SUPPLY

2.4

Detailed recommendations for air supply are given in BS6644. The following notes are
given as guidance.

AIR SUPPLY BY NATURAL VENTILATION

2.4.1

The purpose provided space housing the boiler(s) must have permanent air vents commu-
nicating directly with the outside air, at high level and at low level. Were communications
with the outside air is possible only by means of high level air vents, ducting down to
floor level for the lower vent(s) should be used. For an exposed boilerhouse, air vents
should be fitted, preferably on all four sides but at least on two sides. Air vents should
have negligible resistance and must not be sited in any position where they are likely to
be easily blocked or flooded or in any position adjacent to an extraction system which is
carrying inflammable vapour. Grilles or louvres should be so designed that high velocity
air streams do not occurr within the space housing the boiler(s).
The air supply requirements stated below are related to the maximum rated heat INPUT
of the boiler(s) and are equivalent to those specified in BS6644.
The total minimum free area requirements of the air vent are as follows:

Total input rating

Position of

Air Vent areas

of boiler installation

Air vent(s)

(Air direct from outside)

Up to 2 MW

High level

270 cm

2

plus 2.25 cm

2

per 

(outlet)

kilowatt in excess of 60 kW 
total rated input (gross)

Содержание REGENCY 4 MODULEK Series

Страница 1: ...R E G E N C Y 4 R E G E N C Y 4 INSTALLATION AND SERVICING INSTRUCTIONS FROM 9 TO 16 SECTION BOILERS COD 1274061 M O D U L E K M O D U L E K...

Страница 2: ......

Страница 3: ...table for heating large dwellings commercial or industrial buildings They are designed for use on pumped circulation systems and if used for hot water production calorifiers indirect cylinders plate h...

Страница 4: ...ilers of rated inputs between 60 kW and 2 MW IGE UP 2 Gas installation pipework boosters and compressors on industrial and commercial premises CIBSE Guide Reference sections B7 B11 and B13 British Gas...

Страница 5: ...2 4 Air supply 2 4 1 Air supply by natural ventilation 2 4 2 Air supply by mechanical ventilation 2 5 Gas connection 2 6 Water connection 2 6 1 System water treatment 2 7 Flue hood assembly 2 8 Draug...

Страница 6: ......

Страница 7: ...d off the damper shuts down the chimney avoiding heat losses through the chimney with one firing burner the damper partially closes to avoid eccessive secondary air from passing through the boiler wit...

Страница 8: ...t 300 R 1 1 4 160 710 75 1450 210 Regency 4 186 11 sect 300 R 1 1 4 260 860 75 1650 310 Regency 4 203 12 sect 300 R 1 1 4 160 810 75 1650 210 Regency 4 220 13 sect 300 R 1 1 4 260 960 75 1850 310 Rege...

Страница 9: ...20 20 20 20 20 20 pressure GPL G30 mbar 30 30 30 30 30 30 30 30 GPL G31 mbar 37 37 37 37 37 37 37 37 Burner Natural gas mbar 11 5 11 5 11 5 11 5 11 5 11 5 11 5 11 5 pressure GPL G30 mbar 29 0 29 0 29...

Страница 10: ...rmostat Overrun relay High limit thermostats Thermometer External flue hood Unassembled casing Contacts arrangement for external controls Option to operate in the two stage or in the on off mode Optio...

Страница 11: ...26X N I4 0Y I4 6Xe7 I4 6K f V4 6X h V 1 N L V 1 3 1 1 3 I4 0M I K I 6K eJ I4 Kh V4 3 1 V L V L N N L 0M V V4 6KO 1 I 6Kg V N X N 1 5 1 V4 I V 6Xf V 3 1 3 O 3 L I4 V4 V4 K eJ V4 N L V4 X L N 1 I I I 6K...

Страница 12: ...604 19 REDUCING BUSH 1 1 2x1 2 8588801 20 FRONT SECTION 1230000 21 RIGHT SUPPORT FOOT 0634304 21 LEFT SUPPORT FOOT 0634305 22 PIPE FIXING BRACKET 0648000 23 GAS FEED PIPE 1251509 1251510 1251511 12515...

Страница 13: ...SETBUTTON FOR RESETTING THE FRONT IONISATION CONTROL 14 REAR BURNER SWITCH FOR ON OFF OPERATION OF REAR BURNER 15 IONISATIONRESETBUTTON FOR RESETTING THE REAR IONISATION CONTROL 16 PUMP OVERRUN CONTRO...

Страница 14: ...REGENCY 4 MODULEK 255 750 mm 750 mm REGENCY 4 MODULEK 272 800 mm 800 mm The boiler is delivered as a consignment of four packages It is supplied complete with a draught diverter which must be fitted...

Страница 15: ...with a wire mesh to pro tect against blockage The terminal should not be sited adjacent to any opening window air vent or other ventilation opening and should be situated at least 1 m above the roof s...

Страница 16: ...r Regency 4 Modulek 237 Low Level 1615 cm2 per boiler High level 856 cm2 per boiler Regency 4 Modulek 255 Low Level 1712 cm2 per boiler High level 907 cm2 per boiler Regency 4 Modulek 272 Low Level 18...

Страница 17: ...the circulating water particularly where the system type is open vented The fill water will almost always produce a scale deposit on the waterways of the boiler This deposit will reduce the heat tran...

Страница 18: ...e aprons 6 to the front and rear plates using the stud and nut fi xings both aprons are delivered with the casing in a separate carton Insert the two multi bar burners into the combustion chamber and...

Страница 19: ...able bush pro vided and then insert it through the slots of same bracket screw the motor cable connector into the socket fixed on the bottom of control panel BEWARE the motor has been already wired an...

Страница 20: ...ep to terminals 48 49 and the switch of the 2nd step to terminals 50 51 The overrun relay fitted avoids boiler nuisance trip of the limit safety thermostat when the cir culating pump is stopped with a...

Страница 21: ...ELECTRICAL DIAGRAM REGENCY 4 152 272 9 16 SECTION BOILERS 15...

Страница 22: ...16...

Страница 23: ...17...

Страница 24: ...18...

Страница 25: ...19...

Страница 26: ...20...

Страница 27: ...21...

Страница 28: ...internal fold to the brackets 6 secure the link side panel to the front fixing bracket 5 using the screws F 4 2 x 9 5 pro vided secure the right side panel to the front fixing bracket 5 using the two...

Страница 29: ...e that gas system is completely purged of air pilot coil of front gas control valve is energised 24Vcc Should the front pilot burner light and ignition electrode should continue to spark and if after...

Страница 30: ...he main rear burner shall light Attach manometer to front burner pressure test point and turn on gas supply Turn on the front switch When front burner is fully ignited and stable adjust gas pressure o...

Страница 31: ...for obstruction To clean the boiler outer case use a damp dusting cloth only Warning always turn off the electrical supply before proceeding Do not use detergents or solvents To remove particularly re...

Страница 32: ......

Отзывы: